System bus (CAN) with Servo PLC & Drive PLC
Configuration (AIF interface)
4-3
l
PLC-Systembus EN 1.1
4.4
Process data object identifiers
The identifiers for the process data objects XCAN1_IO ... XCAN3_IO are composed of the so-called
basic identifier and the node address set in C2350:
Identifier
=
Basic identifier
+
node address
Basic identifier
dec
hex
PDOs
XCAN1_IO (cyclic process data)
XCAN1_IN
512
200
XCAN1_OUT
384
180
XCAN2_IO (event or time-controlled process data)
XCAN2_IN
640
280
XCAN2_OUT
641
281
XCAN3_IO (event or time-controlled process data)
XCAN3_IN
768
300
XCAN3_OUT
769
301
4.4.1
Assignment of individual identifiers
For bigger system bus networks with many participants it might be useful to set individual identifiers
for the process data objects XCAN1_IO ... XCAN3_IO via C2353/C2354 that are independent of the
node address set in C2350:
1. Set C2353/x to “ 1”
(x = subcode of the corresponding process data object):
Code
LCD
Possible settings
Info
Lenze Choice
C2353 XCAN addr sel
0
Identifier assignment via C2350 + basic
identifier
1
Identifier assignment via C2354/x
Source for the identifiers of the
process data objects
•
Save changes with C0003 = 1
•
Changes will only become
effective after a reset node!
1 XCAN addr sel1
0
XCAN1_IN/OUT
2 XCAN addr sel2
0
XCAN2_IN/OUT
3 XCAN addr sel3
0
XCAN3_IN/OUT
2. Set the value that results in the desired identifier when adding “ 384” in C2354/x
(x = subcode of the corresponding process data object):
Code
LCD
Possible settings
Info
Lenze Choice
C2354 XCAN addr
0
{1}
1663 Defining individual identifiers for
the process data objects
1
2
3
4
5
6
IN1 addr2
OUT1 addr2
IN2 addr2
OUT2 addr2
IN3 addr2
OUT3 addr2
129
1
257
258
385
386
XCAN1_IN
XCAN1_OUT
XCAN2_IN
XCAN2_OUT
XCAN3_IN
XCAN3_OUT