5.5.3.3
Optimising the Imax controller
Using the Lenze setting of the current limitation controller, the drive is stable:
Most applications do not require optimisation.
The setting of the current limitation controller must be adapted if
power control including great moments of inertia is performed.
– Recommendation: Increase of the reset time Ti (
) of the I
max
controller.
vibrations occur in the V/f control (V encoder) mode during the intervention of
the current limitation controller.
– Recommendation: Increase of the reset time Ti (
) of the I
max
controller.
overcurrent errors occur due to load impulses or too high acceleration ramps.
– Recommendation: Reduction of the gain Vp (
) of
the I
max
controller
Note!
V
min
boost is automatically calculated by the motor parameter identification
using the data specified on the motor nameplate so that a no-load current of
approx. 0.8 I
rated motor
results at the slip frequency of the machine.
V/f control (V encoder)
If V/f control (V encoder) is selected, we recommend a decidedly lower
V
min
boost:
• In this case, select a V
min
boost which ensures that approx. 50 % of the rated
motor current flows at slip frequency when the motor is idling.
Parameter
Info
Lenze setting
Value Unit
VFC: Vp Imax controller
0.25
VFC: Ti Imax controller
65 ms