Electrical installation
Standard devices in the power range of 55 kW
Motor connection
150
EDK82EV903 DE/EN/FR 5.1
5.4.4
Motor connection
Danger!
ƒ
All control terminals only have basic insulation (single isolating distance)
after connecting a PTC thermistor or a thermal contact.
ƒ
Protection against accidental contact in case of a defective isolating
distance is only guaranteed through external measures, e. g. double
insulation.
U
V
W
PE
T1
T2
U, V, W,
PE
15 Nm
132 lb-in
M 8
PE
T1
T2
2,5 Nm
22.1 lb-in
PE
PE
M
3~
M
3~
PTC
PE
PES
PE
U
V
W
T1
T2
J>
PES
PES
PES
PES
PES
PES
1
0
3 Nm/26.5 lb-in
M5 × 12
8200vec286
Place the shield of the motor cables with shield clamp and M5 × 12 mm screws onto the shield
sheet.
Strain relief with cable binders.
Use low−capacitance motor cables! (Core/core
£
190 pF/m, core shield
£
320 pF/m)
The shorter the motor cable, the better the drive behaviour!
PES
HF shield termination by PE connection through shield clamp.
T1,
T2
Terminals of motor temperature monitoring with PTC thermistor or thermal contact (NC
contact).
Lay a separate cable (shielded) to X2/T1 and X2/T2 for motor temperature monitoring.
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!
Lay the control and mains cables separately from the motor cable!
Cable cross−sections U, V, W, PE
8200 vector
mm
2
AWG
ÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑ
E82xV453K4B
ÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑ
50
1
ÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑ
E82xV553K4B
ÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑ
50
0