2.5-inch hot-swap drive and drive backplane replacement
Use this procedure to install or remove 2.5-inch hot-swap drives and drive backplanes.
Remove a drive backplane
Use this procedure to remove a drive backplane.
Before removing the drive backplane:
1. Read the safety information and installation guidelines (see “Safety” on page iii and “Installation
2. Turn off the server and peripheral devices and disconnect the power cords and all external cables (see
“Power off the server” on page 8).
3. If the server is installed in a rack, slide the server out on its rack slide rails to gain access to the top
cover, or remove the server from the rack.
4.
Watch the procedure
. A video of this procedure is available from the following links:
• https://www.youtube.com/playlist?list=PLYV5R7hVcs-B2y7oAb54mfyuLrIusa_qE
• http://list.youku.com/albumlist/show/id_50483449
5. Remove the top cover (see “Remove the top cover” on page 130).
To remove the drive backplane, complete the following steps:
Step 1. Pull all the drives and fillers out slightly to disengage them from the backplane.
Step 2. Remove the fan cage assembly (see “Remove the fan cage assembly” on page 61).
Step 3. Disconnect all the signal cables and the power cable from the backplane.
Step 4. Lift and hold the retention latches on top of the backplane
Figure 42. Drive backplane removal
Step 5. Rotate the backplane from the top toward the center of the server to disengage it from the retention
latches.
If you are instructed to return the component or optional device, follow all packaging instructions, and use
any packaging materials for shipping that are supplied to you.
54
ThinkSystem SR850 Maintenance Manual
Summary of Contents for ThinkSystem SR850
Page 1: ...ThinkSystem SR850 Maintenance Manual Machine Type 7X18 and 7X19 ...
Page 8: ...vi ThinkSystem SR850 Maintenance Manual ...
Page 58: ...50 ThinkSystem SR850 Maintenance Manual ...
Page 142: ...134 ThinkSystem SR850 Maintenance Manual ...
Page 166: ...158 ThinkSystem SR850 Maintenance Manual ...
Page 170: ...162 ThinkSystem SR850 Maintenance Manual ...
Page 174: ...Taiwan BSMI RoHS declaration 166 ThinkSystem SR850 Maintenance Manual ...
Page 176: ...168 ThinkSystem SR850 Maintenance Manual ...
Page 182: ...174 ThinkSystem SR850 Maintenance Manual ...
Page 183: ......
Page 184: ...Part Number SP47A24295 Printed in China 1P P N SP47A24295 1PSP47A24295 ...