Step 1. Open the bracket on the PCIe riser-card assembly.
Step 2. Align the adapter with the connector on the PCIe riser-card assembly.
Step 3. Push the adapter into the PCIe riser-card assembly until it clicks into place.
Figure 92. Adapter installation to the PCIe riser-card assembly
Step 4. Close the bracket.
After installing an adapter in a PCIe riser-card assembly, complete the following steps:
1. If the adapter is installed to a PCIe riser-card assembly, install the PCIe riser-card assembly to the server
(see “Install the PCIe riser-card assembly” on page 88).
2. Reinstall the top cover (see “Install the top cover” on page 131).
3. Reconnect the power cords and any cables that you removed.
4. Install the server in the rack.
5. Power on the server and any peripheral devices.
Power supply unit replacement
Use this procedure to install or remove power supply units.
Remove a hot-swap power supply unit
Use this procedure to remove a hot-swap power supply unit.
S002
CAUTION:
.
Hardware replacement procedures
93
Summary of Contents for ThinkSystem SR850
Page 1: ...ThinkSystem SR850 Maintenance Manual Machine Type 7X18 and 7X19 ...
Page 8: ...vi ThinkSystem SR850 Maintenance Manual ...
Page 58: ...50 ThinkSystem SR850 Maintenance Manual ...
Page 142: ...134 ThinkSystem SR850 Maintenance Manual ...
Page 166: ...158 ThinkSystem SR850 Maintenance Manual ...
Page 170: ...162 ThinkSystem SR850 Maintenance Manual ...
Page 174: ...Taiwan BSMI RoHS declaration 166 ThinkSystem SR850 Maintenance Manual ...
Page 176: ...168 ThinkSystem SR850 Maintenance Manual ...
Page 182: ...174 ThinkSystem SR850 Maintenance Manual ...
Page 183: ......
Page 184: ...Part Number SP47A24295 Printed in China 1P P N SP47A24295 1PSP47A24295 ...