To install a hot-swap drive, complete the following steps:
Watch the procedure
. A video of the installation and removal process is available:
• YouTube:
https://www.youtube.com/playlist?list=PLYV5R7hVcs-DTDY1lmpIPpJVOzo7dKq14
• Youku:
http://list.youku.com/albumlist/show/id_52222446.html
Figure 88. Hot-swap drive installation
Step 1. Ensure that the drive tray handle is in the open position. Slide the drive into the drive bay until it
snaps into position.
Step 2. Close the drive tray handle to lock the drive in place.
Step 3. Check the drive status LED to verify that the drive is operating correctly.
• If the yellow drive status LED is lit continuously, that drive is faulty and must be replaced.
• If the green drive activity LED is flashing, the drive is being accessed.
Step 4. Continue to install additional hot-swap drives if necessary.
After installing all hot-swap drives:
1. Reinstall the security bezel. See “Install the security bezel” on page 100.
2. Use the Lenovo XClarity Provisioning Manager Lite to configure the RAID if necessary. For more
information, see:
https://sysmgt.lenovofiles.com/help/topic/lxpml_v2/Introduction.html
OCP 3.0 Ethernet adapter replacement
Use this information to remove and install the OCP 3.0 Ethernet adapter.
Note:
The OCP 3.0 Ethernet adapter is available only on some models.
Remove the OCP 3.0 Ethernet adapter
Use this information to remove the OCP 3.0 Ethernet adapter.
Ground package before opening”
CAUTION:
.
Hardware replacement procedures
113
Summary of Contents for ThinkSystem SR635
Page 1: ...ThinkSystem SR635 Maintenance Manual Machine Types 7Y98 and 7Y99 ...
Page 5: ...Index 231 Copyright Lenovo 2019 2021 iii ...
Page 6: ...iv ThinkSystem SR635 Maintenance Manual ...
Page 10: ...viii ThinkSystem SR635 Maintenance Manual ...
Page 12: ...Figure 2 QR code 2 ThinkSystem SR635 Maintenance Manual ...
Page 22: ...12 ThinkSystem SR635 Maintenance Manual ...
Page 88: ...78 ThinkSystem SR635 Maintenance Manual ...
Page 133: ...Figure 102 Riser 1 assembly LP FHFL removal Chapter 3 Hardware replacement procedures 123 ...
Page 136: ...Figure 105 Riser 1 assembly LP FHFL installation 126 ThinkSystem SR635 Maintenance Manual ...
Page 214: ...204 ThinkSystem SR635 Maintenance Manual ...
Page 232: ...222 ThinkSystem SR635 Maintenance Manual ...
Page 240: ...230 ThinkSystem SR635 Maintenance Manual ...
Page 245: ......
Page 246: ......