To install the ThinkSystem NE0152T RackSwitch in a standard equipment rack, complete the following
steps:
Step 1. Locate, record, and retain the product switch information in order to configure and register your
product.
Step 2. Attach a mounting bracket (item 1 in the illustration) to each side of the switch with M4 screws (item
2). Torque the screws to approximately 2.0 newton‐meters (Nm) ± 0.1 Nm (17.7 inch‐pounds).
Figure 25. Attaching mounting brackets to switch
Step 3. From the front, slide the switch into the rack at the desired height.
Step 4. Secure the switch unit to the rack posts with M6 screws (item 3 in illustration), washers (item 6), and
either clip nuts (item 4) or cage nuts (item 5). Torque the screws to approximately 5.7 Nm ± 0.1 Nm
(50 inch‐pounds).
Figure 26. Securing switch to rack posts
44
Lenovo ThinkAgile CP Hardware Installation Guide
Summary of Contents for ThinkAgile CP 4000 Series
Page 1: ...Lenovo ThinkAgile CP Hardware Installation Guide Models CP4000 CP6000 ...
Page 4: ...ii Lenovo ThinkAgile CP Hardware Installation Guide ...
Page 6: ...iv Lenovo ThinkAgile CP Hardware Installation Guide ...
Page 8: ...vi Lenovo ThinkAgile CP Hardware Installation Guide ...
Page 26: ...18 Lenovo ThinkAgile CP Hardware Installation Guide ...
Page 70: ...Figure 42 X Link option 1 topology 62 Lenovo ThinkAgile CP Hardware Installation Guide ...
Page 73: ...Figure 44 X Link topology option 2A Chapter 3 ThinkAgile CP Setup 65 ...
Page 78: ...70 Lenovo ThinkAgile CP Hardware Installation Guide ...
Page 80: ...72 Lenovo ThinkAgile CP Hardware Installation Guide ...
Page 82: ...74 Lenovo ThinkAgile CP Hardware Installation Guide ...
Page 83: ......
Page 84: ......