D1012/D1024 Hardware Installation and Maintenance Guide
11
•
Ideally, use two people to lift an enclosure. However, one person can safely lift an enclosure if its
weight is reduced by removing the power supply modules and disk drive modules.
•
Do not place enclosures in a vertical position. Always install and operate the enclosures in a horizontal
(level) orientation.
•
When installing enclosures in a rack, make sure that any surfaces over which you might move the rack
can support the weight. To prevent accidents when moving equipment, especially on sloped loading
docks and up ramps to raised floors, ensure you have a sufficient number of helpers. Remove obstacles
such as cables and other objects from the floor.
•
To prevent the rack from tipping, and to minimize personnel injury in the event of a seismic occurrence,
securely anchor the rack to a wall or other rigid structure that is attached to both the floor and to the
ceiling of the room.
Electrical guidelines
•
These enclosures work with single-phase power systems having an earth ground connection. To reduce
the risk of electric shock, do not plug an enclosure into any other type of power system. Contact your
facilities manager or a qualified electrician if you are not sure what type of power is supplied to your
building.
•
Enclosures are shipped with a grounding-type (three-wire) power cord. To reduce the risk of electric
shock, always plug the cord into a grounded power outlet.
•
Do not use household extension cords with the enclosures. Not all power cords have the same current
ratings. Household extension cords do not have overload protection and are not meant for use with
computer systems.
Ventilation requirements
Refer to
on page 13 for detailed environmental requirements.
•
Do not block or cover ventilation openings at the front and rear of an enclosure. Never place an
enclosure near a radiator or heating vent. Failure to follow these guidelines can cause overheating and
affect the reliability and warranty of your enclosure.
•
Leave a minimum of 15.2 cm (6 inches) at the front and back of each enclosure to ensure adequate
airflow for cooling. No cooling clearance is required on the sides, top, or bottom of enclosures.
•
Leave enough space in front and in back of an enclosure to allow access to enclosure components for
servicing. Removing a component requires a clearance of at least 38.1 cm (15 inches) in front of and
behind the enclosure.
Cabling requirements
•
Keep power and interface cables clear of foot traffic. Route cables in locations that protect the cables
from damage.
•
Route interface cables away from motors and other sources of magnetic or radio frequency
interference.
•
Stay within the cable length limitations.
•
Storage Enclosures are suitable for connection to intra-building or non-exposed wiring or cabling only.
•
Storage Enclosures are suitable for installation in Network Telecommunication Facilities and locations
where the NEC applies. Enclosures are not suitable for Outside Plant (OSP) installations.
Physical requirements
The floor space at the installation site must be strong enough to support the combined weight of the rack,
Storage Enclosures and any additional equipment. The site also requires sufficient space for installation,
operation, and servicing of the enclosures, together with sufficient ventilation to allow a free flow of air to
all enclosures.
show enclosure dimensions and weights. Enclosure designators are described below.
Enclosure weights assume the following configuration characteristics:
•
2U12 enclosure (LFF):
• “2U12” denotes the 3.5" 12-Storage Enclosure (with ESMs)