XP25
Configuring Unit
When installing a new or replacement outdoor control, the unit selection code may have to be manually assigned using the
7-segment display and push button on the control. The unit code sets unit type, capacity and outdoor fan RPM.
Outdoor control is in
IDLE
mode
(No heating or cooling demand)
To enter
unit selection code
,
push and hold button next
7-segment display until
dash
symbol appears and
immediately release button.
Once dash starts flashing,
proceed to next step.
Turn room thermostat
to
OFF
Push and hold button until the solid
sequence is displayed on the
7-segment display, then
immediately release the button. This
configuration sequence allows the
installer to choose the unit selection
code (number combination) that
matches the outdoor unit type and
inverter.
If three horizontal bars display in any
part of the 7-segment display string
during power-up, the outdoor
control did not store the unit
selection code. If this occurs, the
configuration sequence for that
section of the display string must be
repeated.
Yes
No
−
−−
_
_
−
−
−
NOTE: The
sequence repeats
5 times. If a selection is not made,
the control returns to idle mode.
NOT
SELECTED
SELECTED
Configuring Unit Selection Code
Power-up
- Unit selection code (two-digit number) displayed
represents unit size code (outdoor unit capacity).
During initial power-up, firmware version, unit type, unit capacity
and unit selection code appears on the 7-segment display.
2
4
6
7
9
11
13
14
2-TON HEAT PUMP (XP25-024)
3-TON HEAT PUMP (XP25-036)
4-TON HEAT PUMP (XP25-048)
5-TON HEAT PUMP (XP25-060)
2-TON AIR CONDITIONER (XC25-024)
3-TON AIR CONDITIONER (XC25-036)
4-TON AIR CONDITIONER (XC25-048)
5-TON AIR CONDITIONER (XC25-060)
SELECTED
NOT
SELECTED
UNIT SELECTION
CODE
1.
When the correct unit section code is displayed, release but
ton immediately. [Display begins flashing]
2.
Push and hold button until selection stops flashing during
one of the three cycles. [Release push button]
3.
If selection is not made during those three cycles the control
returns to idle mode.
The outdoor control stores the unit type, automatically exits the con
figuration mode and resets.
If three horizontal bars are shown in the 7-segment display
during power-up, the outdoor control did not store the last
configuration setting. If this happens, the configuration se
quence for that setting must be repeated.
UNIT SELECTION
CODES
Press and hold the button during
the
cycling display.
UNIT
EXAMPLE 7-SEGMENT DISPLAY STRING
FIRMWARE
VERSION
UNIT
TYPE
UNIT
CAPACITY
UNIT
CODE
.
IDLE MODE
(NO DEMAND)
.
Figure 22. Configuring Unit Selection Code