background image

Page 25

XC14 SERIES

CHECKING AIR FLOW AT INDOOR COIL

Check airflow using the Delta−T (

D

T)

 process using the illustration in figure 20.

1. Determine the desired 

D

T

Measure entering air temper-

ature using dry bulb (

A

) and wet bulb (

B

). 

D

T

 is the intersect-

ing value of 

A

 and

 B

 in the table (see triangle).

2. Find temperature drop across coil

Measure the coil’s dry

bulb entering and leaving air temperatures (

A

 and 

C

). Tem-

perature Drop Formula: (

T

Drop

) = 

A

 minus 

C

.

3. Determine if fan needs adjustment

If the difference between

the measured 

T

Drop

 and the desired 

D

T

 

(T

Drop

D

T) 

is within

+3º, no adjustment is needed. See examples: Assume 

D

T

 =

15 and 

A

 temp. = 72º, these 

temperatures would necessi-

tate stated actions:

  T

Drop

D

T

=

ºF

ACTION

53º

 19

15

=

4

Increase the airflow

58º

14

15

=

−1

(3º range) no change

62º

10

15

=

−5

Decrease the airflow

4. Adjust the fan speed

See indoor unit instructions to in-

crease/decrease fan speed.

Changing air flow affects all temperatures; recheck tempera-
tures to confirm that the temperature drop and 

D

T are within

+3º.

D

T

80

24 24 24 23 23 22 22 22 20 19 18 17 16 15

78

23 23 23 22 22 21 21 20 19 18 17 16 15 14

76

22 22 22 21 21 20 19 19 18 17 16 15 14 13

74

21 21 21 20 19 19 18 17 16 16 15 14 13 12

72

20 20 19 18 17 17 16 15 15 14 13 12 11 10

70

19 19 18 18 17 17 16 15 15 14 13 12 11 10

57 58 59 60 61 62 63 64 65 66 67 68 69 70

Temp.
of air
entering
indoor
coil ºF

INDOOR
COIL

DRY

BULB

DRY

BULB

WET

BULB

B

T

Drop

19º

A

Dry−bulb

Wet−bulb ºF

A

72º

B

64º

C

53º

air flow

air flow

All temperatures are
expressed in ºF

Figure 20. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart

WEIGH IN

Liquid Line

Set Diameter

Ounces per 5 feet (g per 1.5 m)

adjust from 15 feet (4.6 m) line set*

3/8" (9.5 mm)

3 ounce per 5’ (85 g per 1.5 m)

 *If line length is greater than 15 ft. (4.6 m), add this amount. If
line length is less than 15 ft. (4.6 m), subtract this amount.

Refrigerant Charge per Line Set Length

NOTE  The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.

CHARGING METHOD

NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the
temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.

CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE

If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the
unit. To calculate the total refrigerant charge:

Amount specified on

nameplate

Adjust amount. for variation

in line set length listed on

line set length table below.

Total charge

+

=

64ºF (17.7ºC) and Below

Figure 21. Using HFC−410A Weigh In Method

Summary of Contents for XC13 Series

Page 1: ...low the brazing technique illustrated starting on page 12 to avoid damaging the service valve s internal seals INSTALLATION INSTRUCTIONS Elite Series XC14 Units AIR CONDITIONER 506636 01 07 11 Superse...

Page 2: ...ove XC14 024 230 35 889 30 1 2 775 35 889 13 7 8 352 7 3 4 197 3 1 4 83 27 1 8 689 3 5 8 92 4 1 2 114 20 5 8 524 XC14 030 230 39 991 XC14 036 230 39 991 XC14 042 230 31 787 XC14 041 230 39 991 XC14 04...

Page 3: ...SUCTION LINE MUFFLER HIGH PRESSURE SWITCH S4 COMPRESSOR HARNESS GROUND LUG SINGLE POLE CONTACTOR 1POLE K1 1 DUAL RUN CAPACITOR C12 CONTROL PANEL PLUMBING AND SWITCHES COMPONENTS COMPRESSOR DISCHARGE...

Page 4: ...loss during shipping and handling Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench or stripping the valve stem recess See the Lennox Service and Application Note...

Page 5: ...2 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench...

Page 6: ...ssure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction pressur...

Page 7: ...ss has a very high level of sound transmission For proper placement of unit in relation to a window see the provided illustration in figure 5 detail A PLACING UNIT ON SLAB When installing unit at grad...

Page 8: ...wo 2 degrees or two inches per five feet 50 mm per 1 5 m away from building structure MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL Outside Unit Placement Slab Mounting at Ground Level SAME FASTENERS...

Page 9: ...ERED PANEL REMOVAL Remove the louvered panels as follows 1 Remove two screws allowing the panel to swing open slightly 2 Hold the panel firmly throughout this procedure Rotate bottom corner of panel a...

Page 10: ...nnox L15 sweat non flare series line set or field fabricated refrigerant line sizes as listed in table 2 NOTE When installing refrigerant lines longer than 50 feet see the Lennox Refrigerant Piping De...

Page 11: ...R RAFTER AT 8 FEET 2 43 METERS INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices sho...

Page 12: ...razing alloys and flux contain materials which are hazardous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and pro...

Page 13: ...FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT...

Page 14: ...structions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DA...

Page 15: ...on valve and the two Teflon rings H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD IN...

Page 16: ...LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY A Remove the field provided fitting that temporary reconnected the liquid line to the indoor unit s distributor assembly B Install one of the provided...

Page 17: ...nder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the li...

Page 18: ...d indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F Wh...

Page 19: ...Refer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wiring and properly sized disconnect switch NOTE Units are approved for use onl...

Page 20: ...s XC13 XC13 XC13 XC13 XC13 XC13 XC13 Figure 14 24VAC Control Wiring Diagrams Field Installed HIGH PRESSURE SWITCH S4 CRANKCASE THERMOSTAT S40 CRANKCASE HEATER HR1 DUAL RUN CAPACITOR C12 FAN MOTOR B4 C...

Page 21: ...TECTION SWITCH S5 OR S173 HIGH PRESSURE SWITCH S4 CRANKCASE THERMOSTAT S40 CRANKCASE HEATER HR1 DUAL RUN CAPACITOR C12 FAN MOTOR B4 COMPRESSOR B1 CONTACTOR K1 GROUND LUG Figure 16 Typical Factory Wiri...

Page 22: ...Page 22 506636 01 Figure 17 Typical Unit Wiring Diagram...

Page 23: ...ly at the disconnect switch The voltage must be within the range listed on the unit s nameplate If not do not start the equipment until you have consulted with the power company and the voltage condit...

Page 24: ...anifold gauge set connected to unit Thermometers to measure outdoor ambient temperature to measure liquid line temperature to measure suction line temperature TXV FIXED ORIFICE APPROACH OR SUBCOOLING...

Page 25: ...14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10 57 58 59 60 61 62 63 64 65 66 67 68 69 70 Temp of air entering indoor coil F INDOOR COIL DRY BULB DRY BULB WET BULB B TDrop 19 A Dry bulb We...

Page 26: ...igh in or remove refrigerant based upon line length SC Subcooling Values F 1 0 C 0 6 BLOCK OUTDOOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the airfl...

Page 27: ...heat SH VAP _____ SAT ______ SH ______ 11 Record the wet bulb temperature air entering indoor coil WB _______ 12 Record outdoor ambient temperature 13 Compare results with table to the left If value i...

Page 28: ...9 395 151 421 152 406 149 420 146 418 145 110 43 426 150 420 148 422 148 446 151 424 153 447 153 430 150 447 148 444 146 115 46 457 153 447 150 449 150 480 152 453 155 476 154 460 152 473 150 471 147...

Page 29: ...coil Consult your installing contractor for proper intervals procedures for your geographic area or service contract INDOOR UNIT 1 Clean or change filters 2 Adjust blower speed for cooling Measure the...

Page 30: ...ner manual for instructions on how to operate your thermostat Preservice Check If your system fails to operate check the following before calling for service Verify room thermostat settings are correc...

Reviews: