background image

9

The table below lists possible causes and solutions to some of the most common problems. Please review this information 

before calling for service.

Symptom

Possible Cause

Possible Solution

Unit does not start.

•  Power failure.
•  Power to unit is OFF or disconnected.
•  Circuit breaker may be tripped or 

fuse may be blown.

•  Remote control batteries may have 

lost their charge or unit controller 

may have malfunctioned.

•  Wait for power to be restored.
•  Turn on or reconnect power to the unit.
•  Reset circuit breaker or replace fuse.
•  Replace batteries in remote control. 

Check controller for proper function.

Indoor fan is operating; 

however, air is not cool.

•  Temperature not properly set at con-

trol.

• 

Compressor may be kept off by delay.

•  Check temperature setting at control.
•  Wait for delay to expire.

Unit cycles on and off frequently.

•  Refrigerant charge is incorrect.
•  Air in refrigerant circuit.
•  Compressor malfuction.
•  Improper voltage.
•  System refrigerant circuit is blocked.

•  Check for refrigerant leaks and prop-

erly charge system.

•  Evacuate and properly charge system.
•  Check compressor and replace, if ne-

cessary.

•  Check with utility company to provide 

proper voltage.

•  Clear blockage.

Unit not cooling properly.

•  Indoor and/or outdoor coil are dirty.
• 

Air filter is dirty.

• 

Air flow around indoor and/or outdoor 

unit is obstructed.

•  Doors and/or windows are open.
• 

Direct  sunlight  is  affecting  indoor 

tem perature.

•  Heat source inside is placing a large 

burden on the system.

•  Suction pressure is low due to 

possible refrigerant leak.

•  Clean indoor and/or outdoor coil.
• 

Clean or replace air filter.

•  Remove obstructions.
•  Close doors and windows.
•  Use curtains or blinds to block direct 

sunlight.

•  Reduce burden of heat source.
•  Check for refrigerant leaks and prop-

erly charge system.

Unit not heating properly.

•  Doors and/or windows are open.
•  Suction pressure is low due to 

possible refrigerant leak.

•  Close doors and windows.
•  Check for refrigerant leaks and prop-

erly charge system.

Fan speed cannot be changed.

•  Check the mode listed on the unit dis-

play. Fan speed cannot be changed 

in the AUTO or DRY mode.

•  Fan speed cannot be changed in 

AUTO or DRY mode. Change mode to 

COOL, FAN ONLY or HEAT.

Remote control signal is not 

being trans mitted, even when 

ON/OFF button is pressed.

•  Batteries may have lost their charge. •  Replace batteries.

The TEMP adjustment indicator 

is not available.

•  Check the mode listed on the unit 

dis 

play. Temperature cannot be 

adjusted in the FAN ONLY mode.

•  Change the mode to COOL, HEAT or 

DRY.

Operation indicator disappears 

from the display after a period 

of time.

•  Check to see if display reads TIMER 

OFF.

•  Timed operation is terminated at the 

end of the TIMER period.

TIMER ON disappears from the 

display after a period of time.

•  Check to see if display reads TIMER 

OFF.

•  Timed operation is terminated when 

time period has expired.

No tones being sounded by 

indoor unit, even when ON/OFF 

button is pressed.

•  Infra-red receiver must be able to see 

signal from remote control.

•  Batteries may have lost their charge.

•  Aim remote control infra-red transmit-

ter directly at receiver.

•  Replace batteries.

Summary of Contents for VRF V22B Series

Page 1: ...High Static Concealed Duct Units VCFB Ceiling or Floor Mounted Non Ducted Unit VVCB Air Handler USER S MANUAL VRF SYSTEMS Indoor Units 507922 02 05 2019 VRF Indoor Units THIS MANUAL MUST BE LEFT WITH...

Page 2: ...f the unit and all other appliances that may cause a spark Call a licensed professional HVAC technician or equivalent to repair the leak DO NOT spray water on the indoor unit for any reason Do not tou...

Page 3: ...DIFFUSER LOUVER ADJUSTMENT LEVER VCFB Ceiling or Floor Mounted Non Ducted Unit RETURN AIR DISCHARGE AIR LOUVER AIR FILTER VWMB Wall Mounted Non Ducted Unit RETURN AIR GROUNDING SCREW In control box DI...

Page 4: ...HIB High Static Concealed Duct RIGHT SIDE VIEW LIQUID PIPE GAS PIPE AIR FLOW SUPPLY AIR DUCT OPENING AUXILIARY DRAIN CONNECTION Either Side PRIMARY DRAIN CONNECTION Either Side RETURN AIR DUCT OPENING...

Page 5: ...charge air louvers downward during heating and outward during cooling VCFB Ceiling or Floor Mounted Units Use the wired controller or the remote control to set the position of the discharge air louver...

Page 6: ...heck the filter more frequently if the unit is installed in an area with a large amount of dust The filter may be removed and cleaned or it should be replaced with a filter of like kind and size if it...

Page 7: ...uld be held with the air entering side face down when using clean water to wash the filter Filter should be set aside to air dry after cleaning Do not place filter in direct sunlight or use any type o...

Page 8: ...nitiated the opera tion light is lit to signal normal operation The PRE DEF indicator may be lit as well The indoor unit fan will not operate until the indoor coil reaches a pre set temperature This p...

Page 9: ...the system Suction pressure is low due to possible refrigerant leak Clean indoor and or outdoor coil Clean or replace air filter Remove obstructions Close doors and windows Use curtains or blinds to...

Page 10: ...odes will alternate so that all codes are shown Make note of the code E1 EE etc then reset the display by pressing the ON OFF button on the wireless remote controller Press the ON OFF button a second...

Page 11: ...lowly EEPROM ERROR NOTES LED FLASHING SLOWLY 1 FLASH PER SECOND LED FLASHING FAST 2 FLASHES PER SECOND Shown on Indoor Unit Receiver LED Display Error Code Description FE No address E0 Mode conflict E...

Page 12: ...12 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Reviews: