19.3. Outdoor Unit Spot Check Function
There is a check switch in outdoor PCB. Push the switch SW1 to check the states of unit when the unit is running. The digital
display tube will display the follow procedure when push SW1 each time.
SW1
Figure 63. SW1 Location
Table 3. Status Indicators
Display
Remark
0
Normal Display
Display running frequency, running state or malfunction code
1
Quantity of indoor units in good connection
Actual data
Display
Number of indoor units
1
one
2
two
3
three
4
four
5
five
2
Outdoor unit running mode
Off: 0, Fan only: 1, Cooling: 2, Heating: 3, Forced cooling: 4
3
Indoor unit A capacity
The capacity unit is horse power. If the indoor unit is not connected, the digital display
tube will show: “――”
(9K:1HP,12K:1.2HP,18K:1.5HP)
4
Indoor unit B capacity
5
Indoor unit C capacity
6
Indoor unit D capacity
7
Indoor unit E capacity