135
Error Code:
EE
Description:
Water-level alarm malfunction. (For M22A, M33A/B and MMDA units)
General Note:
If the sampling voltage is not 5V, the LED will display the failure.
Power off, then restart the unit 3 minutes
later. Is it still displaying the error code?
If the water-level switch is inserted well?
Yes
No
No
Insert the water-level
switch well.
If the water-level switch is broken?
Replace the water pump, If malfunction is
still not solved.
Replace the indoor main PCB.
Yes
Replace the water-level
switch.