10
Technical Information
Service Manual
2.4 Cooling and Heating Data Sheet in Rated Frequency
Cooling:
Rated cooling
condition(°F) (DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Compressor
revolution
(rps)
Indoor
Outdoor
P (
PSIG
)
T1 (°F)
T2 (°F)
80/66.9
95/-
12K
123.2~145
in:46~52
out:52~57
in:122~176
out:99~109
Suprt High
High
58
80/66.9
95/-
18K
130~142
in:46.4~51.8
out:51.8~57.2
in:167~181.4
out:98.6~118.4 Super High
High
73
80/66.9
95/-
24K
130~142
in:46.4~51.8
out:51.8~57.2
in:167~181.4
out:98.6~118.4 Super High
High
75
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 24.6ft.
Heating:
Rated heating
condition(°F) (DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Compressor
revolution
(rps)
Indoor
Outdoor
P (
PSIG
)
T1 (°F)
T2 (°F)
70/60
19.94/19.04
12K
362.3~435
in:122~176
out:99~109
in:34~37
out:36~41
Super High
High
56
70/60
19.94/19.04
18K
507~550
in:167~181.4
out:98.6~113
in:33.8~37.4
out:35.6~42.8
Super High
High
75
70/60
19.94/19.04
24K
507~550
in:167~181.4
out:98.6~113
in:33.8~37.4
out:35.6~42.8
Super High
High
80
Summary of Contents for LI012CI-160P432-1
Page 104: ...101 Installation and Maintenance Service Manual...
Page 116: ...113 Installation and Maintenance Service Manual...
Page 117: ...114 Installation and Maintenance Service Manual...
Page 118: ...115 Installation and Maintenance Service Manual...
Page 119: ...116 Installation and Maintenance Service Manual...
Page 120: ...117 Installation and Maintenance Service Manual...