6. Diagnosis for compressor synchronism (AP1 below is control board of outdoor unit)
Main detection point:
● If the system pressure is over-high?
● If the work voltage is over-low?
Malfunction diagnosis process:
If the compressor wire COMP(UVW) is well
connected, the connection sequence
forwards to clockwise direction?
Check if the fan
terminal OFAN is
connected well
Replace
compressor
If the outdoor fan works
normally?
If the stop time of
compressor is more than
3min
Synchronism after
energize the unit
and start it
Connect
wire well
Synchronism
occurred during
operation
Replace
control board
AP1
If the radiating of unit is
well?
Remove
malfunction?
Improve the radiating
of unit (clean heat
exchanger and
increase ventilation)
Replace fan
capacitor C1
Replace
outdoor fan
Y
N
N
N
Y
Y
N
Replace
control board
AP1
Remove
malfunction?
Replace
compressor
Y
N
N
Y
If the input voltage of unit
is normal?
Start to run until the
power resume normal
voltage
N
If the refrigerant is too
much?
Charge the
refrigerant with
service manual
Y
Y
N
Y
End
End
Summary of Contents for LI009HI-230P432
Page 33: ...30 Technical Information Service Manual no display...
Page 34: ...31 Technical Information Service Manual...
Page 35: ...32 Technical Information Service Manual battery Cover of battery box remove reinstall...
Page 61: ...58 Installation and Maintenance Service Manual...
Page 69: ...66 Installation and Maintenance Service Manual...
Page 126: ...123 Installation and Maintenance Service Manual...