ELECTRICAL DATA
LGH156H
LGH180H
LGH210H
LGH240H
LGH300S
1
Voltage - 50hz - 3 phase with neutral
380/420V
380/420V
380/420V
380/420V
380/420V
Compressor 1
Rated Load Amps
6.3
6.3
7.8
6.3
8
Locked Rotor Amps
55
55
51.5
55
67.1
Compressor 2
Rated Load Amps
6.3
6.3
7.8
6.3
8
Locked Rotor Amps
55
55
51.5
55
67.1
Compressor 3
Rated Load Amps
6.3
6.3
8
6.3
10.6
Locked Rotor Amps
55
55
67.1
55
74
Compressor 4
Rated Load Amps
- - -
- - -
- - -
6.3
10.6
Locked Rotor Amps
- - -
- - -
- - -
55
74
Outdoor Fan
Motors
Number of motors
3
4
6
6
6
Full Load Amps
1.3
1.3
1.3
1.3
1.3
(total)
(3.9)
(5.2)
(7.8)
(7.8)
(7.8)
Power Exhaust
With (2) 0.25 kW
Full Load Amps
1.3
1.3
1.3
1.3
1.3
(total)
(2.6)
(2.6)
(2.6)
(2.6)
(2.6)
Indoor Blower
Motor
kW 1.5 2.2 3.7 2.2 3.7 5.6 2.2 3.7 5.6 3.7 5.6 7.5 3.7 5.6 7.5
Full Load Amps 3.6 5.3 8.2 5.3 8.2 11.7 5.3 8.2 11.7 8.2 11.7 16
8
12
16
2
Maximum
Overcurrent
Protection
Unit Only
30
35
40
35
40
50
45
45
50
50
50
60
60
70
80
With (2) 0.25 kW
Power Exhaust
35
35
40
35
45
50
45
50
60
50
60
70
60
70
80
3
Minimum
Circuit
Ampacity
Unit Only
28
30
34
31
35
39
39
42
47
44
48
54
56
60
66
With (2) 0.25 kW
Power Exhaust
31
33
36
34
37
42
42
44
49
46
51
56
59
66
68
1
Extremes of operating range are plus and minus 10% of line voltage.
2
Heating / Air Conditioning / Refrigeration (HACR) type breaker or fuse.
3
Refer to local codes to determine wire, fuse and disconnect size requirements.