XP16 − 2 to 5 Ton Heat Pump

 / Page 7

INSTALLATION CLEARANCES 

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

See

NOTES

See NOTES

NOTES:

Service clearance of 30 in. (762 mm) must be maintained on one
of the sides adjacent to the control box. 

Clearance to one of the other three sides must be 36 in. (914 mm).

Clearance to one of the remaining two sides may be 12 in. (305
mm) and the final side may be 6 in. (152 mm).

A clearance of 24 in. (610 mm) must be maintained between two
units.

48 in. (1219 mm) clearance required on top of unit.

See

NOTES

See NOTES

Control

Box

OUTDOOR SOUND DATA 

1

U it

Octave Band Sound Power Levels dBA, re 10

−12

 Watts

1

Sound

R ti

Unit

Model No.

Center Frequency − HZ

Rating

Number

Model No.

63

125

250

500

1000

2000

4000

8000

Number

(dB)

XP16-024

79.0

72.0

70.0

69.5

68.5

63.5

58.0

56.5

74

XP16-036

80.5

70.5

71.5

71.0

68.5

63.5

58.5

53.5

76

XP16-048

81.0

72.5

71.5

73.0

70.5

66.0

60.5

58.5

76

XP16-060

80.5

72.5

73.5

77.5

72.5

67.0

62.5

58.5

78

NOTE − the octave sound power data does not include tonal correction.

1

Tested according to ARI Standard 270-95 test conditions.

FIELD WIRING 

DISCONNECT

SWITCH

(By Others)

OPTIONAL
OUTDOOR

THERMOSTAT

A  Two Wire Power (see Electrical Data)

B  Two or Three Wire Power (size to heater capacity)

C  Twelve Wire Low Voltage  18 ga. minimum

    Fourteen Wire Low Voltage with Optional Outdoor Thermostat

D  Eight Wire Low Voltage  18 ga. minimum

 Ten Wire Low Voltage with Optional Outdoor Thermostat

 Field Wiring Not Furnished  

All wiring must conform to NEC or CEC and local electrical codes.

LENNOX

INDOOR UNIT

OPTIONAL

ELECTRIC

HEAT

THERMOSTAT

(Optional)

LENNOX

OUTDOOR

UNIT

DISCONNECT

SWITCH

(By Others)

A

B

C

D

Summary of Contents for Elite XP16024

Page 1: ...upersedes June 2007 SEER up to 17 0 2 to 5 Tons Cooling Capacity 23 200 to 58 500 Btuh Heating Capacity 21 200 to 54 000 Btuh MODEL NUMBER IDENTIFICATION P16 036 Unit Type P Heat Pump Series Nominal C...

Page 2: ...ionS SEER up to 17 0 Heating COP up to 3 82 HSPF region IV up to 8 70 2 through 5 ton Single phase power supply Sound levels as low as 74 dB Vertical air discharge allows concealment behind shrubs at...

Page 3: ...Senses suction line temperature and cycles the compressor off when suction line temperature falls below it s setpoint Opens at 29 F and closes at 58 F Refrigerant Line Kits Refrigerant lines suction l...

Page 4: ...thout any additional controls Kit can be added in the field enabling unit to operate properly down to 30_F A Freezestat should be installed on compressors equipped with a low ambient kit A Compressor...

Page 5: ...ull load amps 1 1 1 1 1 7 1 8 Fan Motor Locked rotor amps 2 2 1 3 1 2 9 OPTIONAL ACCESSORIES must be ordered extra ComfortSenset 7000 Thermostat Y0349 S S S S Outdoor Temperature Sensor for ComfortSen...

Page 6: ...D LINE CONNECTION D G K J E F UNIT SUPPORT FEET XP16 036 TO 060 BASE SECTION H Model No A B C D E F G H J K Model No in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm XP16 024 31 787 27 686...

Page 7: ...16 024 79 0 72 0 70 0 69 5 68 5 63 5 58 0 56 5 74 XP16 036 80 5 70 5 71 5 71 0 68 5 63 5 58 5 53 5 76 XP16 048 81 0 72 5 71 5 73 0 70 5 66 0 60 5 58 5 76 XP16 060 80 5 72 5 73 5 77 5 72 5 67 0 62 5 58...

Page 8: ...F C33 24B 2 CX34 18 24C 6F C33 24C 2 CX34 19A 6F C33 19A 2 CX34 25A 6F C33 25A 2 CX34 25B 6F C33 25B 2 CX34 30A 6F C33 30A 2 CX34 30B 6F C33 30B 2 CX34 30C 6F C33 30C 2 CX34 31A 6F C33 31A 2 CX34 31B...

Page 9: ...7 70 6 70 2010 1845 1625 3 40 2 30 CX34 25B 6F 4 G61MPV 36B 045 Factory TXV 24 000 21 600 12 900 16 00 11 70 7 70 6 70 2010 1815 1605 3 48 2 36 CX34 36B 6F 4 G61MPV 36B 045 Factory TXV 24 200 21 200...

Page 10: ...H33 36B 2F 4 G60UHV 36B 090 2 49L24 24 000 21 400 12 800 16 20 12 00 7 70 6 70 1990 1790 1580 3 50 2 38 CH33 36B 2F 4 G61MPV 36B 045 2 49L24 24 200 21 400 12 700 16 20 12 20 8 00 6 70 1955 1740 1550 3...

Page 11: ...65 2370 3 52 2 48 CR33 50 60C F 4 G61MPV 36C 090 2 49L24 36 400 33 200 20 000 16 00 12 00 8 50 7 20 3005 2765 2370 3 52 2 48 CR33 50 60C F 4 G71MPP 36C 090 2 49L24 Horizontal Indoor Coils Horizontal C...

Page 12: ...8 000 52 000 33 200 14 70 11 20 8 20 7 20 5105 4935 4350 3 08 2 24 CBX26UH 060 Up Flow Horizontal Factory TXV 56 500 52 500 33 200 15 20 11 20 8 50 7 20 4985 4710 4115 3 26 2 36 4 CBX27UH 060 Up Flow...

Page 13: ...7 20 5075 4780 4155 3 24 2 36 CR33 50 60C F 4 G71MPP 60C 110 2 91M02 55 500 53 500 34 200 14 50 10 60 8 50 7 50 5235 4855 4270 3 22 2 34 CR33 50 60C F 4 G61MPV 60C 090 2 91M02 55 500 53 500 34 200 14...

Page 14: ...SIONS Sections Description of Change ARI Ratings New rating for XP16 048 with CX34 62D coil and CX34 62D coils with furnaces ARI Ratings Removed CB30U ratings ARI Ratings Add ratings with G71MPP furna...