Lennox Allied Air EFV Series Installation Instructions Manual Download Page 8

0650329-56 / 506265-03

Issue 1924

Page 8 of 13

Sequence of Operation

Cooling (cooling only or heat pump)

Single Stage Cooling

For single stage cooling, Y1 and Y2 need to be jumpered.

When the thermostat calls for cooling, the circuit between R 

and G is completed, and the blower relay is energized. The 

Normally Open contacts close, causing the indoor blower 

motor  to  operate.  The  circuit  between  R  and  Y  is  also 

completed; this circuit closes the contactor in the outdoor 

unit starting the compressor and outdoor fan motor. Circuit 

R and O energizes the reversing valve switching it to the 

cooling position. (The reversing valve remains energized 

as long as selector switch is in the COOL position.)

Two Stage Cooling

On a call for 1st stage cooling, the thermostat closes R 

to Y. In 1st stage cooling, the blower runs at 70% of the 

selected cooling airflow. On a call for 2nd stage cooling, 

the thermostat closes R to Y2. In 2nd stage cooling, the 

blower runs at 100% of the selected cooling airflow.

Heating (electric heat only)

When the thermostat calls for heat, the circuit between R 

and W is completed, and the heater sequencer is energized. 

A time delay follows before the heating elements and the 

indoor  blower  motor  come  on.  Units  with  a  second  heat 

sequencer  can  be  connected  with  the  first  sequencer  to 

W on the thermostat sub-base or connected to a second 

stage on the sub-base.

Heating (heat pump)

When the thermostat calls for heat, the circuits between R 

and Y and R and G are completed. Circuit R-Y energizes 

the contactor starting the outdoor fan motor and the 

compressor.  Circuit  R  and  G  energizes  the  blower  relay 

starting the indoor blower motor.

If the room temperature should continue to fall, the 

circuit  between  R  and  W1  is  completed  by  the  second 

stage heat room thermostat. Circuit R-W1 energizes 

a  heat  sequencer.  The  completed  circuit  will  energize 

supplemental  electric  heat.  Units  with  a  second  heater 

sequencer  can  be  connected  with  the  first  sequencer  to 

W1 on the thermostat or connected to a second heating 

stage W2 on the thermostat sub-base.

Emergency Heat (heating heat pump)

If  selector  switch  on  thermostat  is  set  to  the  emergency 

heat  position,  the  heat  pump  will  be  locked  out  of  the 

heating circuit, and all heating will be electric heat. A jumper 

should  be  placed  between  W2  and  E  on  the  thermostat 

sub-base so that the electric heat control will transfer to the 

first stage heat on the thermostat. This will allow the indoor 

blower to cycle on and off with the electric heat when the 

fan switch is in the AUTO position.

Summary of Contents for Allied Air EFV Series

Page 1: ...ded for use by qualified service technicians familiar with safety procedures and equipped with the proper tools and test instruments Failure to carefully read and follow all instructions in this manual can result in equipment malfunction property damage personal injury and or death WARNING Disconnect all power supplies to both the indoor blower section and outdoor section before making any electri...

Page 2: ... rating plate for specific information These electric furnaces are completely factory assembled and all components are performance tested Each unit consists of a blower assembly optional refrigerant coil and controls in an insulated galvanized factory finished enclosure and may also include electric heat as specified Knockouts are provided for electrical power wiring entrance When used on cooling ...

Page 3: ... blower If an elbow is included in the plenum close to the unit it must not be smaller than the dimensions of the supply duct flange on the unit Non Ducted Return Closet Installation The cabinet can be installed in a closet with a false bottom to form a return air plenum or be installed with a return air plenum under the unit Louvers or return air grilles are field supplied Local codes may limit a...

Page 4: ... codes before connecting drain line to an existing drainage system Insulate drain lines where sweating could cause water damage The removal of cabinet knockouts required for drain connections can be made much easier with the indoor coil assembly removed from the cabinet Install drain lines so they do not block service access to front of unit A 24 clearance is required for filter coil or blower rem...

Page 5: ... 240 volt single phase 60 cycle AC power supply The units are internally factory wired for 240 volt installation If 208 volt installation is desired it will be necessary to change the black transformer lead in the blower cabinet control box to the 208V terminal on the transformer The variable speed motor in the EFV electric furnace contains DC filter capacitors that will cause a surge or inrush of...

Page 6: ...t the O wire to the 24 volt R wire The motor control board that provides airflow selection also features LED indicators that display operating mode humidity control and airflow CFM In addition thermostat signals for emergency heat EM aux heat W1 reversing valve O compressor stage 1 Y1 compressor stage 2 Y2 and blower G are all indicated by lit LED s on this board If a humidistat is used the dehumi...

Page 7: ...00 Emer Heat X X 1600 1400 1200 1100 EFV20DCP Cont Blower X 900 800 700 600 Cooling X X 1800 1600 1400 1200 Heating X 1800 1600 1400 1200 Aux Heat X X 1800 1600 1400 1200 Emer Heat X X 1800 1600 1400 1200 This CFM is not approved for use with highest kW heater size Humidistat will reduce cooling airflow by 10 in high humidity Air flow is greater of COOL and HEAT when both electric heat and heat pu...

Page 8: ...g elements and the indoor blower motor come on Units with a second heat sequencer can be connected with the first sequencer to W on the thermostat sub base or connected to a second stage on the sub base Heating heat pump When the thermostat calls for heat the circuits between R and Y and R and G are completed Circuit R Y energizes the contactor starting the outdoor fan motor and the compressor Cir...

Page 9: ...Is the unit circuit breaker s rotated properly ON up OFF down Are all access panels in place and secure Refer to outdoor unit installation instructions for system start up instructions and refrigerant charging instructions Airflow For proper system operation the airflow through the indoor coil should be between 350 450 CFM per ton of cooling capacity Each electric furnace is shipped configured to ...

Page 10: ...nd dust IMPORTANT See unit position figures for location of filter in unit cabinet and service panel giving access to unit filter Inspect air filters at least once a month and replace or clean as required Dirty filters are the most common cause of inadequate heating or cooling performance Replace disposable filters Washable filters can be cleaned by soaking in mild detergent and rinsing with cold ...

Page 11: ...0650329 56 506265 03 Issue 1924 Page 11 of 13 Airflow Configurations Left to Right Airflow Right to Left Airflow Upflow Counterflow Horizontal Figure 3 Airflow Configurations ...

Page 12: ...0650329 56 506265 03 Issue 1924 Page 12 of 13 Figure 4 Wiring Diagram Variable Speed Blower ...

Page 13: ...Air Conditioning with or without Electric Heat Electric Furnace Thermostat Air Condensing Unit R R O C C1 C W2 EM W1 W1 Y2 Y2 Y1 Y1 Y1 G G 2nd Stage Electric Heat if used 1st Stage Electric Heat if used 2 Stage System only for single stage systems jumper Y1 to Y2 Connect O to R for proper cooling blower delay Y Y2 Heat Only Electric Furnace Thermostat R R C C1 W2 EM W1 W1 G G 2nd Stage Electric He...

Reviews: