background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

8

Step 8. Fireplace should be secured to side
framing members using the full length nailing
tabs at the top and bottom of the fireplace front
face.  Use 8d nails or equivalent (

Figure 17 ).

Figure 17

Note: The nailing tabs and the area directly
behind the nailing tabs are exempt from the
clearances described on page 5.  Maintain at
least 1/2" clearance from the firebox wrapper to
the framing at the closest point of contact,
directly adjacent to the flange.

Figure 18

Step 3. Position appropriate firestop spacer at
ceiling and fasten temporarily with two (2) 8d
nails or equivalent. If chimney penetrates ceil-
ing vertically, use flat firestop spacer, Model
F8FS-2 for FTF8 system and Model F10FS-2
for the FTF10 system*. If chimney penetrates
ceiling at 30

°

 angle (offset chimney), use 30

°

firestop spacer, Model F8FS30-2 for FTF8 and
Model F10FS30-2 for FTF10 system*. Use one
nail on opposite sides to hold firestop spacer
in position.  Fasten permanently, using at least
two (2) more 8d nails or equivalent, after
chimney sections have been assembled
through the firestop spacer and after any nec-
essary adjustments have been made. Firestop
spacer must be secured by at least four (4) 8d
nails or equivalent when completely installed.

Note: If there is a room above ceiling level,
firestop spacer must be installed on the bottom
side of the ceiling. If an attic is above ceiling
level, firestop spacer must be installed on top
side of ceiling joist (Figures 19 and 20 ).

Figure 19

Figure 20

Firestop Spacer

Room Above

Firestop Spacer

Attic Above

INSTALLING THE CHIMNEY SYSTEM

Step 1. Before continuing, check the operation
of the damper, as described on page 4, (

refer

to Figure 3 ).

Step 2. Using standard construction framing
techniques, construct opening for chimney
route up through the ceiling(s) and roof or
through an outside chase.

Framing must maintain adequate minimum air
space clearance at all times.

CAUTION: ALLOW MINIMUM 2" (51 MM)
CHIMNEY AIR SPACE TO COMBUSTIBLE
FRAMING MEMBERS THROUGHOUT VERTI-
CAL OR OFFSET CHIMNEY INSTALLATION
(

SEE **NOTE ).

A minimum 2" (51 mm) air space must be
reserved for all combustible materials ex-
tending for any continuous length surround-
ing the chimney (

See **Note).

Reference 

Figures 14 and 15 and charts Fram-

ing Dimensions for Ceiling and Roof, which
specify minimum ceiling and roof dimensions.

To determine chimney center line in new con-
struction, use plumb line from roof or ceiling
above fireplace to center of flue collar on
fireplace.

For remodeling, plumb to center of flue collar
from ceiling above, drive nail through ceiling
from below to mark position, then mark and
cut to passage from above ceiling (around
nail) (

Figure 18 ). Then plumb from ceiling or

roof level directly above hole which has just
been completed.

Step 6. Route the Class 0 air duct out the back
wall or side wall, up through the ceiling or floor
joists to an outside wall. The air duct should be
located above snow level.

Note: If the fireplace is installed against an
inside wall, the Class 0 air duct may be ex-
tended into a ventilated attic space at least 18"
(457 mm) above the attic floor. Secure the duct
hood to a vertical post with the inlet positioned
downward. Ensure nothing blocks the hood
opening. This air duct must never terminate
higher than the chimney.

Step 7. Cut or frame hole through the outside
wall for the installation of the duct inlet hood.
A 4 

¹⁄₄

" (114 mm) diameter hole is sufficient.

Feed the loose end of the flexible air duct
through the hole cut for the inlet hood and
attach to collar on inlet hood using two (2)
screws. Insert hood into opening. Secure in
place with nails driven through holes in hood
flange. Seal with noncombustible waterproof
silicon type caulking. If additional air duct is
needed, use Class 0 metallic air duct.

*Note: Use Models F10FS or F10FS30 when
installing FTF10 chimney in the U.S. only.

** Note: 1"  (25 mm) when installed with FTF10
in the U.S. only.

Plumb Line

Note: If installing the optional collar duct kit, it
should be installed after the chimney has been
attached to the flue collar.

8d Nail Or

Equivalent

Summary of Contents for Merit CR-3835L

Page 1: ...y circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and approvals of thi...

Page 2: ...afe distance from the fireplace 8 NEVER leave children unattended when there is a fire burning in the fireplace 9 Always keep flue damper open when heat is present in the fireplace 10 Before servicing...

Page 3: ...BOCA Basic National Codes the Standard Me chanicalCodeandtheUniformBuildingCodes When complete these fireplace systems con sists of five basic sub systems 1 The Fireplace 2 The Chimney and Termination...

Page 4: ...re firestopping at the ceiling levels for outside chase installa tions However it is recommended for safety and the reduction of heat loss Figure 5 Chase Enclosure A chase is a vertical box like struc...

Page 5: ...n Each installation is unique however and might require a different sequence 1 Position firebox prior to framing or into prepared framing 2 Install the chimney system 3 Connect house wiring to the fir...

Page 6: ...2 mm Class 0 air duct provided to the collar on the chimney collarenclosurewiththescrewsprovidedinthe hardware kit IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 6 BE REMOVED OR...

Page 7: ...432mm 610 mm 483mm 660 mm Perpendicular to roof ridge A B Ceiling Framing C D Roof Framing Framing Without False Header Header B A C Outside Corner C A Back Wall of Chase Encloslure Including Finishi...

Page 8: ...W MINIMUM 2 51 MM CHIMNEY AIR SPACE TO COMBUSTIBLE FRAMING MEMBERS THROUGHOUT VERTI CAL OR OFFSET CHIMNEY INSTALLATION SEE NOTE A minimum 2 51 mm air space must be reserved for all combustible materia...

Page 9: ...om Above 10 Max Room Above 2 Min Air Space 2 Min Air Space Figure 23 Outer pipe section installs in just the opposite way the lanced end goes down and each new section goes OVER the outside of the pre...

Page 10: ...ote Do not caulk or seal the ventilating openings Step 7 Secure flashing by nailing along the perimeter into roof using 8d nails If shingled roof slide upper end and sides of roof flashing under shing...

Page 11: ...smoke free opera tion Trees buildings adjoining roof lines ad verse wind conditions etc may require a taller chimney should the fireplace not draft properly see Figure 32 MULTIPLE TERMINATIONS If more...

Page 12: ...ng Do not puncture the inner flue Maximum offset of chimney system is 30 Two offsets must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue...

Page 13: ...imney Components Chimney Only Inches Feet Inches 12 18 24 36 48 S4 Meters 247 20 7 0 1 0 0 5 6 29 253 21 1 0 0 1 0 5 6 44 257 21 5 1 1 0 0 5 6 55 263 21 11 1 0 1 0 5 6 70 269 22 5 0 1 1 0 5 6 85 275 2...

Page 14: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Page 15: ...1 1073 2064 44 85 1 1 0 1 1 1 0 1124 2159 45 86 1 1 0 0 1 0 1 1149 2197 47 90 1 1 0 0 2 1 0 1200 2286 48 91 1 1 0 0 0 2 0 1226 2330 49 93 1 1 0 2 1 1 0 1251 2381 51 97 1 1 0 1 4 0 0 1308 2470 53 100 1...

Page 16: ...59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2 1 946 1861 38 75 1 0 0 0 2 972 1905 39 77 1 0 2 1 1 997 1956 41...

Page 17: ...stall the same as chimney sections First snap the inner section INTO the preceding inner section of flue Check connec tion by pulling up slightly to ensure a tight fit Next the outer sections snap loc...

Page 18: ...ed with all fireplaces It is to protect the combustible floor in front of the fireplace from both radiant heat and sparks The hearth extension must extend 8 beyond both sides of the fireplace opening...

Page 19: ...3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Common brick 5 00 20 5 95 6 Cement mortar 5 00 20 5 95 6 Cera...

Page 20: ...T BE SEALED WITH A NON COMBUSTIBLE MATERIAL Calculating Minimum Thickness if Multiple Materials are Used At times it is important to know what combination of materials are acceptable for use as floor...

Page 21: ...e Combination 63L28 FTF8 OR15 Offset Return Elbow 63L34 FTF10 OR15 Starter Section 8345 FTF8 SS Attic Shield Assembly Firestop Spacer 63L67 FTF8 FSAS Canada Only 63L68 FTF10 FSAS 63L10 FTF8 12 63L13 F...

Page 22: ...r Flat 63L36 F10FS 2 Outside Combustion Air Kits with duct 81L87 FOAK without duct 81L88 FOAK LD 63L25 FTF8 S4 Stabilizer 63L26 FTF10 S4 Chimney Pack Conventional 63L70 FTF8 CP7 Contains 3 FTF8 36 1 F...

Page 23: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 23 NOTES...

Page 24: ...850 048M REV N C 01 2007 1110 West Taft Avenue Orange CA 92865 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to disc...

Reviews: