NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

9

Step 4. Two sets of nailing tabs have been
provided.  One set of four is to accommodate

⁵⁄₈

" drywall and the other set is for 

¹⁄₂

" drywall.

To insert the unit into prepared framing, bend
the four nailing flanges adjacent to one of the
fireplace faces completely over 180 degrees
until they are flush with the cabinet.  Bend the
remaining nailing flanges adjacent to the op-
posite face out 90 degrees (

see Figure 18 ).

Slide the unit through the framed opening with
the face adjacent to the flanges bent fully over
180 degrees, inserted first.

Slide the unit into the prepared framing until the
unit is centered between the walls.  Fold the
nailing tabs back against the framing, level the
unit with shims as necessary and secure the
fireplace to the side frame members with 8d
nails or screws as appropriate.

Figure 18

Note: The nailing tabs are exempt from the
fireplace clearances described on the fireplace
clearance label.

INSTALLING THE CHIMNEY SYSTEM

Step 1. Check flue damper for proper opera-
tion. To open, pull handle down and release.
Damper will open automatically. To close, push
handle up.  The damper should lock into the
closed position.

Note: The damper is set to one opening, but
may be switched if necessary.

Step 2. Using standard construction framing
techniques, construct opening for chimney route
up through the ceiling(s) and roof or through an
outside chase.

Framing must maintain adequate minimum air
space clearance at all times.

CAUTION: ALLOW MINIMUM 2" (51 MM)
CHIMNEY AIR SPACE TO COMBUSTIBLE
FRAMING MEMBERS THROUGHOUT VERTI-
CAL OR OFFSET CHIMNEY INSTALLATION.
ALSO MAINTAIN AIR SPACE ON TOP OF THE
FIREPLACE AS DEFINED BY THE SPACERS
AND STANDOFFS.

A minimum 2" (51 mm) air space must be
reserved for all materials extending for any
continuous length surrounding the chimney.

See 

Figures 26 and 27 and charts “Framing

Dimensions for Ceiling and Roof” on page 10,
which specify minimum ceiling and roof di-
mensions.

For new construction, to determine chimney
center line, use plumb line from roof or ceiling
above fireplace to center of flue collar on
fireplace.

For remodeling, plumb to center of flue collar
from ceiling above, drive nail through ceiling
from below to mark position, then mark and
cut to passage from above ceiling (around
nail) (

Figure 19 ). Then plumb from ceiling or

roof level directly above hole which has just
been completed.

Plumb Line

Step 3. Position appropriate firestop spacer at
ceiling and nail temporarily with two (2) 8d
nails. Use flat firestop spacer, Model F10FS-2,
if chimney penetrates ceiling vertically. If chim-
ney penetrates ceiling at 30

°

 angle (offset

chimney), use Model F10FS30-2. Nailed, one
each on opposite sides to hold firestop spacer
in position. Nail permanently, using at least
two (2) more 8d nails, after chimney sections
have been assembled through the firestop
spacer and after any necessary adjustments
have been made. Firestop spacer must be
secured by at least four (4) 8d nails when
completely installed.

Note: If there is a room above ceiling level,
firestop spacer must be installed on the bottom
side of the ceiling. If an attic is above ceiling
level, firestop spacer must be installed on top
side of ceiling joist (Figures 20 and 21).

Figure 20

Figure 21

Figure 19

Firestop Spacer

Room Above

Firestop Spacer

Attic Above

Step 4. 

Note: Chimney sections are con-

structed with a unique locking tab design
which ensures an immediate, tight assembly
between sections. Plan your chimney require-
ments carefully before assembly as chimney
is difficult to disassemble after installation. If
disassembled, the tabs might become dam-
aged. Be certain tabs are properly formed to
ensure tabs engage properly.

Nailing
Flange

Framing
Stud

Summary of Contents for MAGNA-FIRE LS43ST

Page 1: ...ponents under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and...

Page 2: ...ensure a safe fireplace system and to prevent the build up of soot and creosote inspect and clean the fireplace and chimney priortouseandperiodicallyduringtheheating season 5 Use solid fuel only DO N...

Page 3: ...place and chimney system must be enclosed when installed in or passing through a living area where combustibles or people may come in contact with it This is important to prevent possible personal inj...

Page 4: ...er just behind the firebox lintel Figure 3 The control lever snaps into place at the ex treme range of motion up and back in the closed position When pulled forward and down the damper is open Figure...

Page 5: ...d and the fireplace positioned into the opening Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney...

Page 6: ...n 51 mm Platform Metal Safety Strips 2 Min 51 mm Figure 10 Figure 12 Figure 11 IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 10 BE REMOVED OR MODIFIED NOR MAY YOU NOTCH THE HEA...

Page 7: ...TO SCALE 7 Figure 14 Figure 15 Figure 16 FRAMING SPECIFICATIONS 26 667 mm 54 1391 mm 58 1490 mm 47 1197 mm 47 1197 mm 58 1490 mm Front View 54 1391 mm 19 489 mm Allow 19 For Clearance 26 667 mm For D...

Page 8: ...NS Figure 17 27 700 mm Top View Front View End View 27 701 mm 8 216 mm 20 508 mm 44 1121 mm 42 1086 mm Outside Air Inlet This Side Only Gas Line Inlet 9 241 mm 11 298 mm 52 1335 mm 24 625 mm 52 1340 m...

Page 9: ...extending for any continuous length surrounding the chimney See Figures 26 and 27 and charts Framing Dimensions for Ceiling and Roof on page 10 which specify minimum ceiling and roof di mensions For n...

Page 10: ...ing tabs 7 locking tabs per joint Check each piece by pulling up slightly from the top to ensure proper engage ment before installing succeeding sections If the flue has been installed correctly it wi...

Page 11: ...band at the pipe joint Locking bands wrap around pipe joints equally covering the joints of both pipe sections Use nut provided and TIGHTEN snugly Do not over tighten as this might damage chimney sec...

Page 12: ...of the components are LS43ST Fireplace 58 1486 mm FTF13 12 10 260 mm FTF13 18 16 413 mm FTF13 36 34 870 mm CTD Termination 4 102 mm CT1 Termination 18 457 mm CT2 Termination 15 to 23 381 mm 584 mm CTD...

Page 13: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Page 14: ...0 641 1334 26 54 1 0 1 0 1 667 1378 28 57 1 0 0 3 0 718 1467 29 59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2...

Page 15: ...must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue system provided the total height of the system exceeds 22 5 6 m Return elbow support...

Page 16: ...2 and 43 Support the chimney at floor or ceiling pen etration with a FTF13 stabilizer if distance of chimney below ceiling is 10 3 m or more Maintain 2 51 mm minimum air space to combustibles from chi...

Page 17: ...sted and approved to ANSI IAS AGA Z21 11 2 for use with unvented gas appliances and complies with the stan dard for Factory Built fireplaces UL 127 The unit has been tested for use with any unventedga...

Page 18: ...Stone Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Co...

Page 19: ...r lower k value insulating value than k 54 BTU IN FT2 HR F At no time may a perpendicular side wall be located closer than 9 from the fireplace opening If fireplace is installed diagonally across a 90...

Page 20: ...ion 1110 West Taft Avenue Orange CA 92865 INSTALLATION COMPONENTS Offset Return Package 30 63L24 FTF13 ES30 Chase Termination Square 63L54 FTF13 CT2 63L19 FTF13 12 63L20 FTF13 18 Chimney Section 63L21...