background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

10

Check vertical alignment of chimney pipe so
that it projects from the roof in a true vertical
position.  Security's chimney sections do not
need to be screwed together.  Additional rein-
forcement is not necessary, except in certain
offset conditions (see to page 16, 

Figure 47 ).

Step 5. The height of vertical chimney pipe
supported only by the fireplace must not ex-
ceed 30' (9.1 m). Chimney heights above 30'
(9.1 m) must be supported by a Model FTF13-
S4 stabilizer installed at 30' (9.1 m) intervals.

Note: The Model FTF13-S4 adds 3" (76 mm) net
effective height to the total chimney system.

Install the Model FTF13-S4 stabilizer by fitting
inner section down into respective section of
proceeding flue pipe and locking outer stabi-
lizer section into place over the outer chimney
pipe. Position for proper clearance through
framed opening and nail straps securely (un-
der tension in “shear”) into place on framing.
Use 8d nails. Attach successive lengths of
chimney pipe directly to stabilizer using same
techniques as described in Step 4 (

Figure 25 ).

The FTF13 chimney system is a two-piece
chimney, which snaps together from the fire-
place up. Start with the inner flue section. With
the lanced end up, snap-lock it into the match-
ing collar on top of the fireplace. At all subse-
quent joints, the upper flue section fits into the
preceding flue section. Each piece snaps to-
gether by means of locking tabs (7 locking
tabs per joint). Check each piece by pulling up
slightly from the top to ensure proper engage-
ment before installing succeeding sections, If
the flue has been installed correctly, it will not
separate when you test it. Also, the inner flue
joint where each section is joined should be
tight and flat without gaps (

Figure 22 ).

Figure 22

Outer pipe section installs in just the opposite
way; the lanced end goes down and each new
section goes OVER the outside of the previous
section installed (

Figure 23 ).

Locking Tabs

(Lances)

Figure 23

Note: Assemble one component of chimney at a
time (inner section first, then outer section last)
before proceeding with the next complete section.

Continue to assemble the chimney up through
framed ceiling opening.  Assemble just enough
to penetrate the roof flashing openings (

Figure

24 ).  Always maintain 2" (51 mm) minimum air
space to combustible materials and always
check each pipe joint (inner and outer) to
ensure proper engagement.

2" (51mm) Min. Air Space
to Combustibles

Figure 24

Figure 26

Framing Dimensions for Ceiling

Ceiling Opening

Flue Type

A

B

FTF13, Vertical

19"

19"

at 2" (51 mm)

(483 mm)

(483 mm)

FTF13, Offset

19"

29"

At 2" (51 mm)

(483 mm)

(737 mm)

Figure 27

Framing Dimensions for Roof

FTF13 at 2" (51 mm)

Pitch

C

D*

0/12

19"

19"

(483 mm)

(483 mm)

6/12

19"

20"

(483 mm)

(508 mm)

12/12

19"

27"

(483 mm)

(686 mm)

* Perpendicular to Roof Ridge.

A

B

Ceiling Framing

C

D

Roof Framing

FTF13-S4 Stabilizer

Figure 25

Note: Do not apply excessive pressure to any
subsequent chimney sections following the
stabilizer when installing. Ensure each subse-
quent chimney section is securely attached by
testing as noted in Step 4.

Summary of Contents for MAGNA-FIRE LS43ST

Page 1: ...ponents under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and...

Page 2: ...ensure a safe fireplace system and to prevent the build up of soot and creosote inspect and clean the fireplace and chimney priortouseandperiodicallyduringtheheating season 5 Use solid fuel only DO N...

Page 3: ...place and chimney system must be enclosed when installed in or passing through a living area where combustibles or people may come in contact with it This is important to prevent possible personal inj...

Page 4: ...er just behind the firebox lintel Figure 3 The control lever snaps into place at the ex treme range of motion up and back in the closed position When pulled forward and down the damper is open Figure...

Page 5: ...d and the fireplace positioned into the opening Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney...

Page 6: ...n 51 mm Platform Metal Safety Strips 2 Min 51 mm Figure 10 Figure 12 Figure 11 IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 10 BE REMOVED OR MODIFIED NOR MAY YOU NOTCH THE HEA...

Page 7: ...TO SCALE 7 Figure 14 Figure 15 Figure 16 FRAMING SPECIFICATIONS 26 667 mm 54 1391 mm 58 1490 mm 47 1197 mm 47 1197 mm 58 1490 mm Front View 54 1391 mm 19 489 mm Allow 19 For Clearance 26 667 mm For D...

Page 8: ...NS Figure 17 27 700 mm Top View Front View End View 27 701 mm 8 216 mm 20 508 mm 44 1121 mm 42 1086 mm Outside Air Inlet This Side Only Gas Line Inlet 9 241 mm 11 298 mm 52 1335 mm 24 625 mm 52 1340 m...

Page 9: ...extending for any continuous length surrounding the chimney See Figures 26 and 27 and charts Framing Dimensions for Ceiling and Roof on page 10 which specify minimum ceiling and roof di mensions For n...

Page 10: ...ing tabs 7 locking tabs per joint Check each piece by pulling up slightly from the top to ensure proper engage ment before installing succeeding sections If the flue has been installed correctly it wi...

Page 11: ...band at the pipe joint Locking bands wrap around pipe joints equally covering the joints of both pipe sections Use nut provided and TIGHTEN snugly Do not over tighten as this might damage chimney sec...

Page 12: ...of the components are LS43ST Fireplace 58 1486 mm FTF13 12 10 260 mm FTF13 18 16 413 mm FTF13 36 34 870 mm CTD Termination 4 102 mm CT1 Termination 18 457 mm CT2 Termination 15 to 23 381 mm 584 mm CTD...

Page 13: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Page 14: ...0 641 1334 26 54 1 0 1 0 1 667 1378 28 57 1 0 0 3 0 718 1467 29 59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2...

Page 15: ...must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue system provided the total height of the system exceeds 22 5 6 m Return elbow support...

Page 16: ...2 and 43 Support the chimney at floor or ceiling pen etration with a FTF13 stabilizer if distance of chimney below ceiling is 10 3 m or more Maintain 2 51 mm minimum air space to combustibles from chi...

Page 17: ...sted and approved to ANSI IAS AGA Z21 11 2 for use with unvented gas appliances and complies with the stan dard for Factory Built fireplaces UL 127 The unit has been tested for use with any unventedga...

Page 18: ...Stone Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Co...

Page 19: ...r lower k value insulating value than k 54 BTU IN FT2 HR F At no time may a perpendicular side wall be located closer than 9 from the fireplace opening If fireplace is installed diagonally across a 90...

Page 20: ...ion 1110 West Taft Avenue Orange CA 92865 INSTALLATION COMPONENTS Offset Return Package 30 63L24 FTF13 ES30 Chase Termination Square 63L54 FTF13 CT2 63L19 FTF13 12 63L20 FTF13 18 Chimney Section 63L21...

Reviews: