Lennox Hearth Products Elite EDVI25 Installation Instructions Manual Download Page 11

11

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Make gas line connections. All codes require a 
shut-off valve mounted in the supply line. Figure 
18 illustrates two methods for connecting the 
gas supply. The fl ex-line method is acceptable 
in the U.S., however, Canadian requirements 
vary depending on locality. Installation must 
be in compliance with local codes.

Step 9. CONNECTING GAS LINE 

Gas
Stub

¹₂

" x

 

³₈

" Flare

Shut-Off Valve

³₈

" Flex Tubing

³₈

" NPT x 

Flare Fitting

³₈

.IPPLE

³₈

"

 

5NION

³₈

#LOSE.IPPLE

³₈

3HUT/FF6ALVE

¹₂

 

³₈

 

"

Reducer

Gas
Valve

Gas Flex Line Connector

3EDIMENT4RAP
RECOMMENDED 

-IN

Figure 18 - 

GAS CONNECTION

When fi rst lighting the appliance, it will take 
a few minutes for the line to purge  air from 
the appliance. Once purging is complete, the 
pilot and burner will light and operate as indi-
cated in the instruction manual. Subsequent 
lightings of the appliance will not require such 
purging. Inspect the pilot fl ame (remove logs, 
if necessary, handling carefully).

Damper

Gear Clamp

Liner 
Connector
Plate

Combustion 
Air (inlet)

Exhaust (outlet)

Figure 16

Figure 17

Screw

Notes:
• Final gas connection should be made after 
unit is in place to avoid damage to line when 
pushing the unit into position.

• Mill-pac, high temperature silicone and/or 
screws may also be used to secure the liners 
to the collars (gear clamps must also be 
used).

These appliances are equipped with a gas 
fl ex line for use (where permitted) in con-
necting the unit to the gas line.  A gas fl ex 
line is provided to aid in attaching the appli-
ance to the gas supply.  The gas fl ex line 
can only be used where local codes permit. 
See Figure 18 for fl ex line description. The 
fl ex line is rated for both natural and pro-
pane gas. A manual shut off valve is also 
provided with the fl ex line. The gas control 
valve is located in the lower control compart-
ment. The millivolt control valve has a 3/8" 
(10 mm) NPT thread inlet port fi tting. 

Purging Air from Supply Line 

a. Turn gas supply line valve off.
b. Loosen setscrew at inlet pressure tap on 
control valve (see Figure 36).
c. Turn gas supply line valve on.
d. When gas fl ows, turn supply valve off.
e. Close the inlet pressure tap.

Figure 19

Step 11. INSTALLING LOGS, VERMICU-
LITE AND EMBERS

The packaged log set, vermiculite and embers 
are located within the fi rebox of the insert. 
Note: The EDVI25/EDVI30 log set is shown 
in fi gures 20-28 and the EDVI35 log set is 
shown in fi gures 29-34.

Installation Instructions:

Purging Air from Appliance 

Purge air from appliance by holding gas 
control valve down in the pilot position 
until pilot will light (see Figure 19). 

DO NOT 

LIGHT A MATCH IF YOU SMELL GAS. 

Light 

a match then allow gas fl ow to pilot.  If the 
Match “blows”, there is air in the line (purge 
line). If the fl ame is straight and tall, there is 
no gas pressure.

Liner 
Connector
Plate

Note: If an optional Brick Liner Kit was 
purchased, intall it now, per instructions 
provided in kit.

Flex Liner Installation (see Figure 14 for 
Masonry Fireplace Installations and Figure 
15 for Factory Built Fireplaces):

Note: Refer to Vent Manufacturer Instal-

lation Instructions.

1) Cut the fl ex liners as required

 (mark both 

ends of one of the fl exible liners as INLET). 

2) Connect the liner marked INLET to the inlet 
side of the termination adaptor. Connect the 
other liner to the exhaust side. Secure liner 
to INLET collar with hose clamp.

3) Install fl ashing.

4) Insert both liners into chimney, passing 
through the damper opening.

5) Install termination cap.

6) Remove the liner connector plate from the 
insert top (by removing the screw shown in 
Figure 17, then sliding plate backward until it 
clears the retaining breackets).  Liners should be 
streched just enough to prevent the possibility 
of sagging or coiling in the fl ue. Cut off excess 
liner (see collar locations on pages 5 & 6).

7) Connect the liner marked INLET to the inlet 
collar on the liner connector plate (marked 
with an "I"). Connect the remaining liner to 
the exhaust collar (marked with an "E") on 
the liner connector plate. 

Note: Both con-

nections should be secured to collars using 
gear clamps.

8) Slide the liner connector plate all the way 
forward and secure into place with a screw 
(provided) as shown in Figure 16 & 17.

WARNING: If logs are not installed accord-
ing to the directions shown here, fl ame 
impingement and improper combustion 
could occur and result in soot and/or exces-
sive production of carbon monoxide (CO), 
a colorless, odorless, toxic gas

.

AIR PURGING PROCEDURES MUST BE 
PERFORMED BY A QUALIFIED TECHNICIAN 
ONLY.

Step 10. PURGING AIR

Summary of Contents for Elite EDVI25

Page 1: ...USINGPROPERTYDAMAGE PERSONAL INJURY OR LOSS OF LIFE FOR YOUR SAFETY Do not store or use gasoline or other flammable s or liquids in the vicinity of this or any other appliance FOR YOUR SAFETY What to...

Page 2: ...ropane conversion kit if needed to run on LP gas 3 One Warranty Certificate 4 One Fireplace Warning Label Wheninstalledinamanufacturedhome mobile home these appliances must be installed in accordance...

Page 3: ...TO THE FLU WITH HEAD ACHES DIZZINESS AND OR NAUSEA IF YOU HAVE THESE SIGNS OBTAIN FRESH AIR IMMEDIATELY TURN OFF THE GAS SUPPLY TO THE APPLIANCE AND HAVE IT SERVICED BY A QUALIFIED PROFES SIONAL AS IT...

Page 4: ...or Regional Gas Codes National Fuel Gas Code 2 Local amendments 3 Recognized testing lab OMNI Test Labo ratories Inc Beaverton Oregon 4 Is a permit required cost 5 Insomestatesormunicipalities alicen...

Page 5: ...DVI25 Steady State Efficiency 65 NG 66 LP 86 NG 89 LP 110 cfm 5 127 mm 19 1 2 483 mm 1 15 16 49 mm 10 9 16 268 mm 9 5 8 224 mm 1 1 4 32 mm 26 5 8 676 mm 20 1 2 521 mm 14 356 mm N B A D E F C J 17 1 4...

Page 6: ...BTU hr Input LP 22 000 to 28 000 26 000 to 34 000 Co linear DV Vent Size 3 Dia Liner exhaust intake 3 Dia Liner exhaust intake Room Blower CFM EFFICIENCIES EDVI30 EDVI35 Steady State Efficiency 87 NG...

Page 7: ...in Min Min Min Min Min MAX MAX Min Max See Fig 3 4a 0 0 mm 0 0 mm 16 406 mm 16 406 mm 49 1245 mm 48 1219 mm 50 1270 mm 49 1245 mm 36 914 mm 36 914 mm 8 203 mm 8 203 mm 64 1626 mm 64 1626 mm See Fig 3...

Page 8: ...om of Door outward Figure 11 WARNING NEVER OPERATE UNIT WITH OUT THE FRONT GLASS DOOR PANEL IN PLACE AND SECURE DETAILED INSTALLATION STEPS Step 2 PREPARATION Plan and install gas line These appliance...

Page 9: ...ec tor Plate Screw Guide Hose Clamps After liners are secured to collars slide liner con nector plate forward and secure with screw Flex Liner Installation Air Inlet Liner for combus tion air When ter...

Page 10: ...ure 15 Roof Flashing See Direct Vent System Components on Page 9 Use 3 diameter listed liner UL1181 or UL1777 for the AIR INTAKE Use 3 diameter listed liner UL1777 ONLY for the EXHAUST Use 3 diameter...

Page 11: ...NSTALLING LOGS VERMICU LITE AND EMBERS Thepackagedlogset vermiculiteandembers are located within the firebox of the insert Note The EDVI25 EDVI30 log set is shown in figures 20 28 and the EDVI35 log s...

Page 12: ...ins and or log stoppers This will ensure a proper flame and safe combustion 1 Place the largest log onto the 2 corresponding locating pins at the back of the firebox as shown in Figure 20 Figure 20 2...

Page 13: ...entations on Front Center Log and front right twig as shown in Figure 26 Figure 26 Front Center Log Top Right Log Figure 27 Figure 28 Embers Vermiculite Carefully install the seven piece log set into...

Page 14: ...wn in Figure 34 One package of ember material has been included with this log set You will not need to use the entire bag IMPORTANT The quantity and placement of the ember material can affect stove pe...

Page 15: ...TLET DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG IT MUST BE ROUTED TO AVOID CONTACT DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE With gas line installed run initial system checko...

Page 16: ...not soot the shutter opening must be adjusted between these two extremes No smoke or soot should be present Repo sition the logs if flames impinge on any of them If the logs are properly positioned a...

Page 17: ...N 9 1467B SERIAL NUMBER NOMBRE DE SERIE XXX XXX IIIIIIIIIIIIIIIIIIII XXX P N 9 1467B DU DESSUS DE L APPAREIL 12 203mm 305mm Cat No H0921 MAX MAX MODEL NO EDVI30 MANUFACTURED AT Union City TN FOR USE W...

Page 18: ...EL FOR INSTALLATION IN SOLID FUEL FIREPLACES THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE WITH AIR FILTERS FOYER AU GAZ CHAUFFANT AVEC EVACUATION NE DOIT PAS ETRE UTILISE AVEC UN COMBUSTIBLE SOLIDE...

Page 19: ...19 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTE THIS PAGE LEFT BLANK INTENTIONALLY...

Page 20: ...P N 775 156M REV G 3 2005 Lennox reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult you...

Reviews: