background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

10

Masonry Fireplace Installation Diagram

Vertical Term-
ination Cap 
and Flashing. 
Cat. No. 
H0908

Liner Requirements:

Vertical Height Min. = 8 ft. (2.44 M)
Vertical height Max. = 40 ft. (12.2 M)

See Direct Vent System Components 
on Page 9.

Exhaust and air 
Intake collars

Hook up Air 
& Exhaust
as Shown
Here

Air
Intake

Exhaust

Clay 
Chimney 
Liner

Damper plate is 
removed or fastened 
in open position

Masonry chimneys may take 
various contours which the 
fl exible liners will accomodate. 
However, keep the fl exible liner 
as STRAIGHT as possible, avoid 
unnecessary bending.

Figure 14

Before running the fl exible liners, make sure that both liners will pass through 
existing damper area. Remove or lock damper to allow the passage of the fl exible 
liners. If the damper will not allow the passage of both liners, DO NOT PROCEED 
FURTHER (the appliance may NOT be installed into the fi replace)

.

Factory Built Fireplace Installation Diagram

Vertical Termination Cap 
and Flashing, Cat. No. H0908

Liner Requirements:

Vertical Height Min. = 8 ft. (2.44 M)
Vertical height Max. = 40 ft. (12.2 M)

Vertical Termination
Adapter

Storm Collar

Air
Intake

Exhaust

Exhaust and Air 
Intake Collars

Hook up Air & 
Exhaust as
Shown Here

Figure 15

Roof 
Flashing

See Direct Vent System Components 
on Page 9.

Use 3" diameter listed 
liner (UL1181 or UL1777) 
for the AIR INTAKE.

Use 3" diameter listed 
liner (UL1777 ONLY) for 
the EXHAUST

Use 3" diameter listed liner 
(UL1181 or UL1777) for the AIR 
INTAKE.

Use 3" diameter listed gas vent liner 
(UL1777 ONLY) for the EXHAUST

The fl exible vent pipe must 
NOT be allowed to sag behind  
insert or in fi replace fl ue.

The fl exible vent pipe must 
NOT be allowed to sag behind  
insert or in fi replace fl ue.

Read fi replace 

requirements, 

page 4

Read Fireplace 

Requirements on 

page 4

• The Flex Kit, Cat. No. H0909 includes one 35' fl ex liner and four gear clamps.
• The Termination Kit, Cat. No. H0908 includes the termination cap with two 
collinear collars for 3” fl ex attachments and fl ashing.

Make sure that both liners will pass through existing damper area. Remove or lock 
damper to allow the passage of the fl exible liners. If the damper will not allow the 
passage of both liners, DO NOT PROCEED FURTHER.  Consult a local mason for 
removal of the damper without risk of structural damage or leakage.

The standard cap in Termination Kit, H0908, is a 
high wind cap

The standard cap 
in Termination 
Kit, H0908, is a 
high wind cap

• The Flex Kit, Cat. No. H0909 includes one 35' fl ex liner and four gear clamps.
• The Termination Kit, Cat. No. H0908 includes the termination cap with two collinear 
collars for 3” fl ex attachments and fl ashing.

Gear Clamps

Liner

Liner

Gear Clamps

Summary of Contents for Elite EDVI25

Page 1: ...USINGPROPERTYDAMAGE PERSONAL INJURY OR LOSS OF LIFE FOR YOUR SAFETY Do not store or use gasoline or other flammable s or liquids in the vicinity of this or any other appliance FOR YOUR SAFETY What to...

Page 2: ...ropane conversion kit if needed to run on LP gas 3 One Warranty Certificate 4 One Fireplace Warning Label Wheninstalledinamanufacturedhome mobile home these appliances must be installed in accordance...

Page 3: ...TO THE FLU WITH HEAD ACHES DIZZINESS AND OR NAUSEA IF YOU HAVE THESE SIGNS OBTAIN FRESH AIR IMMEDIATELY TURN OFF THE GAS SUPPLY TO THE APPLIANCE AND HAVE IT SERVICED BY A QUALIFIED PROFES SIONAL AS IT...

Page 4: ...or Regional Gas Codes National Fuel Gas Code 2 Local amendments 3 Recognized testing lab OMNI Test Labo ratories Inc Beaverton Oregon 4 Is a permit required cost 5 Insomestatesormunicipalities alicen...

Page 5: ...DVI25 Steady State Efficiency 65 NG 66 LP 86 NG 89 LP 110 cfm 5 127 mm 19 1 2 483 mm 1 15 16 49 mm 10 9 16 268 mm 9 5 8 224 mm 1 1 4 32 mm 26 5 8 676 mm 20 1 2 521 mm 14 356 mm N B A D E F C J 17 1 4...

Page 6: ...BTU hr Input LP 22 000 to 28 000 26 000 to 34 000 Co linear DV Vent Size 3 Dia Liner exhaust intake 3 Dia Liner exhaust intake Room Blower CFM EFFICIENCIES EDVI30 EDVI35 Steady State Efficiency 87 NG...

Page 7: ...in Min Min Min Min Min MAX MAX Min Max See Fig 3 4a 0 0 mm 0 0 mm 16 406 mm 16 406 mm 49 1245 mm 48 1219 mm 50 1270 mm 49 1245 mm 36 914 mm 36 914 mm 8 203 mm 8 203 mm 64 1626 mm 64 1626 mm See Fig 3...

Page 8: ...om of Door outward Figure 11 WARNING NEVER OPERATE UNIT WITH OUT THE FRONT GLASS DOOR PANEL IN PLACE AND SECURE DETAILED INSTALLATION STEPS Step 2 PREPARATION Plan and install gas line These appliance...

Page 9: ...ec tor Plate Screw Guide Hose Clamps After liners are secured to collars slide liner con nector plate forward and secure with screw Flex Liner Installation Air Inlet Liner for combus tion air When ter...

Page 10: ...ure 15 Roof Flashing See Direct Vent System Components on Page 9 Use 3 diameter listed liner UL1181 or UL1777 for the AIR INTAKE Use 3 diameter listed liner UL1777 ONLY for the EXHAUST Use 3 diameter...

Page 11: ...NSTALLING LOGS VERMICU LITE AND EMBERS Thepackagedlogset vermiculiteandembers are located within the firebox of the insert Note The EDVI25 EDVI30 log set is shown in figures 20 28 and the EDVI35 log s...

Page 12: ...ins and or log stoppers This will ensure a proper flame and safe combustion 1 Place the largest log onto the 2 corresponding locating pins at the back of the firebox as shown in Figure 20 Figure 20 2...

Page 13: ...entations on Front Center Log and front right twig as shown in Figure 26 Figure 26 Front Center Log Top Right Log Figure 27 Figure 28 Embers Vermiculite Carefully install the seven piece log set into...

Page 14: ...wn in Figure 34 One package of ember material has been included with this log set You will not need to use the entire bag IMPORTANT The quantity and placement of the ember material can affect stove pe...

Page 15: ...TLET DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG IT MUST BE ROUTED TO AVOID CONTACT DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE With gas line installed run initial system checko...

Page 16: ...not soot the shutter opening must be adjusted between these two extremes No smoke or soot should be present Repo sition the logs if flames impinge on any of them If the logs are properly positioned a...

Page 17: ...N 9 1467B SERIAL NUMBER NOMBRE DE SERIE XXX XXX IIIIIIIIIIIIIIIIIIII XXX P N 9 1467B DU DESSUS DE L APPAREIL 12 203mm 305mm Cat No H0921 MAX MAX MODEL NO EDVI30 MANUFACTURED AT Union City TN FOR USE W...

Page 18: ...EL FOR INSTALLATION IN SOLID FUEL FIREPLACES THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE WITH AIR FILTERS FOYER AU GAZ CHAUFFANT AVEC EVACUATION NE DOIT PAS ETRE UTILISE AVEC UN COMBUSTIBLE SOLIDE...

Page 19: ...19 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTE THIS PAGE LEFT BLANK INTENTIONALLY...

Page 20: ...P N 775 156M REV G 3 2005 Lennox reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult you...

Reviews: