Lennox Hearth Products Direct Vent MPD-33 Series Installation Instructions Manual Download Page 21

21

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

E. Attach Flex Vent to Termination -
Secure Flex
 components can be purchased
separately and attached to bulk lengths of
Secure Flex flexible tubing cut to size at the
job site.   Secure the flexible vent to the Secure
Flex
 terminations in the same manner (see
Figure 41) as it was attached to the adapter.

D. Install Firestop/Spacers at ceilings and walls -
When Secure Flex penetrates a wall or ceiling,
a firestop/spacer is required: use the SF4.5 VF
firestop/spacer for ceilings and the SF4.5 HF
firestop/spacer for walls. See the appropriate
sections and figures shown throughout the
venting section for their installation requirments.

Figure 42

GEAR
CLAMPS

Adapter

(SV4.5RF)

Apply ONLY MIL-PAC BLACK HIGH
TEMPERATURE SEALANT (Catalog No.
10K81) to the outside surface of both
collars of the adapter (be especially
careful to fill the grooves of the outer
collar to be covered by the flexible
pipe) and slide flexible pipe over
inner and outer adapter collars.

NOTE:  OUTER PIPE IS PULLED AWAY TO
SHOW THE DETAIL OF THE INNER PIPE

FLEX VENT

1-3/4 in. (44 mm)
Flexible Pipe and

 Adapter Outer
Collar Overlap

1-3/4 in. (44 mm)
Flexible Pipe and

 Adapter Inner
Collar Overlap

SECURING SCREW

(3 PLACES EQUIDISTANT

JUST BELOW GEAR CLAMP)

Attach Adapter to Appliance

Collar, or Secure Vent Sections

SECURING SCREW

(3 PLACES EQUIDISTANT

JUST BELOW GEAR CLAMP)

5" (127 mm)

Radius Minimum

SF-12 or SF-18 Flexible Vent Section

Figure 41

VERTICAL OR HORIZONTAL VENTING USING

SECURE FLEX

 KITS AND COMPONENTS

Secure Flex venting kits and components may
be used in any venting application where rigid
Secure Vent (SV4.5) direct vent components
can be used.  All restrictions, clearances and
allowances that pertain to the rigid piping apply
to the flexible venting.  

Secure Flex kits may

not be modified; also, under no circumstances
may separate sections of flex pipe  be joined
together
Secure Flex kits may be added to the
end of a vent run made up of rigid Secure Vent
(SV4.5) vent sections provided that doing so
does not violate any of the venting length,
height, routing, horizontal to vertical ratio re-
quirements or clearance considerations de-
tailed in this manual.

Secure Flex kits come with an included adapter
that can be fitted to the appliance collar or the
inclined channel end of the last Secure Vent
(SV4.5) vent section in a rigid system in the exact
same fashion as any other Secure Vent section.
Align the dimpled end of the adapter over the
previously installed section or appliance collar,
adjusting the radial alignment until the four lock-
ing dimples of the adapter are aligned with the
inlets of the four incline channels of the last vent
section or collar.  Push on the adapter until it fully
engages, then twist the adapter clockwise run-
ning the dimples down and along the incline
channels until they seat at the end of the channels.

B. Install the Outer Flex Pipe -
1.
 Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out of
the way.
2.  Apply a bead of Mill-Pac Black (700

°

F) high

temperature sealant - Catalog No. 10K81) to
the outer adapter collar; to the grooves of the
collar which extend approximately 1 inch from
the end and to the flat surface, approximately 1-
3/8

 

inches from the end.

3. Pull and extend the outer flexible vent pipe.
4.  Slide the outer flex pipe over the adapter
collar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of 1

³⁄₄

inches from the end, and that it is free from
damage or tears.
5.  Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adapter
outer collar approximately 3/4

 

inch from the

end of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adapter collar just below the gear clamp to
provide additional security to the connection.

C. Route Flex Vent -
Ensure that the flex vent is properly routed to
provide the required clearance.  Do Not allow
the flexible vent to bend in a radius tighter than
5" (127 mm). Refer to 

Figure 42. Support

horizontal sections of flex with metal straps at
2 foot (0.61 m) intervals.

Attach the flexible vent to the adapter as
follows (see also 

Figure 41):

A. Install the Inner Flex Pipe -
1.
 Install the small  gear clamp loosely around
the inner flexible vent pipe, push it back out of
the way.
2.  Apply a bead of Mill-Pac Black (700

°

F)

high temperature sealant - Catalog No.
10K81)
 to the inner adapter collar, approxi-
mately 1/2

 

inch from the end.

3. Pull and extend the inner flexible vent pipe.
4.  Slide the inner flex pipe over the adapter
collar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of 1

³⁄₄

inch from the end, and that it is free from
damage or tears.
5.  Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adapter
inner collar approximately 

³⁄₄ 

inch from the

end of the flex.
6. Install three screws 120 degrees apart through
the flexible vent pipe and into the adapter collar
just below the gear clamp to provide additional
security to the connection.

Note: 

Secure Flex vent must be attached to Se-

cure Flex terminations only.  DO NOT substitute
Secure Vent terminations or the Secure Vent
adapter for 

Secure Flex components. The collars

of 

Secure Flex terminations and adapters have a

different circumference than that used with the
Secure Vent pipe.  Additionally, Secure Flex
components have an extended length center tube
for use in attaching the flexible vent.

Summary of Contents for Direct Vent MPD-33 Series

Page 1: ...850 014CF Ce manuel d installation est disponible en francais simplement en faire la demande Num ro de la pi ce 850 014CF s l e d o M t l o v i l l i M s l e d o M c i n o r t c e l E M N C 8 2 3 3 T...

Page 2: ...ntsmanu facturedbySecurityChimneysInternationaland Z Flex Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flex master Canada Limited These approved vent system components are lab...

Page 3: ...rving a separate solid fuel burning appliance These heater rated appliances are intended for use as supplemental heaters only Carbon Monoxide Poisoning Early signs of carbon monoxide poisoning are sim...

Page 4: ...ble 2 APPLIANCE AND VENT CLEARANCES The appliance is approved with zero clearance to combustible materials on all sides as de tailed in Table 2 with the following exception When the unit is installed...

Page 5: ...e and do not supersede local codes in any way Install vent according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B14...

Page 6: ...or securing the glass door Remove the door by tilting it outward at the bottom and lifting it up Set the door aside protecting it from inadvertent damage See Figure 53 on page 24 The fireplace should...

Page 7: ...o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e...

Page 8: ...MPD 4540 Models Dimensions D and F occur when one 45 degree elbow is connected directly to the appliance collar MPD and MPDR units D E F A B MPD and MPDT units o N l e d o M A B C D E 8 2 3 3 T D P M...

Page 9: ...3 8 1 5 4 6 1 1 1 6 2 8 7 4 3 6 1 7 7 1 9 3 9 3 6 1 m m 6 4 1 1 3 4 9 0 1 6 3 0 0 1 6 4 1 1 8 7 6 6 8 8 3 4 4 0 2 2 6 7 0 2 2 6 7 6 0 4 Step 3 INSTALL THE VENT SYSTEM General Information Theseinstruc...

Page 10: ...ALL AND SECURELY TIGHTEN COVER PLATE SCREWS COULD RESULT IN LEAKAGE OF FLUEPRODUCTSINTOTHELIVINGSPACE VENTCOVERPLATEANDVENTSEALPLATE MUSTREMAINSECURELYINSTALLEDON UNUSED VENT COLLAR FAILURE TO DO SO C...

Page 11: ...2 5 2 1 8 1 0 1 0 6 0 7 5 9 2 2 5 2 1 9 1 0 0 1 6 0 7 5 2 3 2 5 7 3 9 1 0 0 0 0 5 5 7 3 2 5 7 9 1 1 0 0 0 5 6 5 1 4 2 5 2 1 0 2 0 0 0 7 0 7 6 4 2 5 0 2 1 0 0 7 0 8 2 5 2 1 2 0 1 0 7 0 8 4 6 2 2 2 0 0...

Page 12: ...nd number of elbows required Refer to Vertical Vent Figures and Tables on page 14 and 15 to select the type of vertical installation desired Vent sections are available in net lengths of 4 1 2 114 mm...

Page 13: ...ction to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected ve...

Page 14: ...ed then 4 feet mini mum V vertical vent will be required This table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of...

Page 15: ...V1 Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Example If20feetof H horizontalven...

Page 16: ...Push the vent component against the previous section until it fully engages then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of th...

Page 17: ...the telescopic vent section SV4 5LA as the last vent section For wall thicknesses greater than that shown in Figure 32 refer to Table 4 on page 18 This table lists the additional venting components ne...

Page 18: ...level Note Secure Vent components rigid vent pipe and terminal are shown in the figures SecureFlexcomponents flexibleventpipeand terminal may also be used Note Two45degreeelbowsmaybeusedinplace ofone...

Page 19: ...s meters meters H1 V H Wall Firestop Spacer SV4 5HF Ceiling Firestop Spacer SV4 5VF When using Secure Flex use Firestop Spacer SF4 5HF When using Secure Flex use Firestop Spacer SF4 5VF Example If 20...

Page 20: ...feet of H horizontal run up to a maxi mum horizontal run of 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 35...

Page 21: ...with the inlets of the four incline channels of the last vent sectionorcollar Pushontheadapteruntilitfully engages then twist the adapter clockwise run ning the dimples down and along the incline chan...

Page 22: ...and Honeywell Millivolt Wiring See Figure 43 1 Select any of the following optional con trols appliance mounted rocker switch or wall mounted switch thermostat oroneofthe optional remote control kits...

Page 23: ...G e t i h W l a r t u e N OPENING CONTROL COMPARTMENT DOOR The millivolt control valve has a 3 8 10 mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is f...

Page 24: ...he firebox floor to the door s vee flange Close both the latches securely Electronic Appliance Checkout To light the burner turn ON the optional remote wall switch and turn the gas control switch to t...

Page 25: ...N 8 1 2 3 p o r P 2 1 3 1 Figure 54 The adjustment rod and associated adjustable air shutter is patented technology Flame ad justments can be made quickly and accurately to taste without the need of...

Page 26: ...ent door Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements Note Combustible wall finish materials and or surround mat...

Page 27: ...m 0 1 6 h c n i 4 2 n o i t c e S 3 7 L 7 7 6 3 L 5 4 V S t n e V m m 4 1 9 h c n i 6 3 n o i t c e S 4 7 L 7 7 8 4 L 5 4 V S t n e V m m 9 1 2 1 h c n i 8 4 n o i t c e S 5 7 L 7 7 A L 5 4 V S n o i...

Page 28: ...x e l F r o f n i m r e T l a c i t r e V n o i t c e s r e t p a d A x e l F h t i w 2 1 2 1 r a l l o c t r o p p u s f o o r t n e v d i g i r f o d n a g n i h s a l f f o o r y l b m e s s a r a...

Page 29: ...ecuring screws WARNING THIS CONVERSION KIT SHALL BE INSTALLED BY A QUALIFIED SERVICE AGENCY IN ACCORDANCE WITH THE MANUFACTURER S IN STRUCTIONS AND ALL APPLICABLE CODES AND REQUIREMENTS OF THE AUTHORI...

Page 30: ...re 61 s m e t s y S T I S t l o v i l l i M n o i s r e v n o C s a G e n a p o r P o T l a r u t a N s t i K s l e d o M e p y T t i n U o N g o l a t a C 8 2 3 3 T D P M 8 2 3 3 R D P M t l o v i l...

Page 31: ...On Any Side Of The Hex Fitting b Attach manometer to the manifold side pressure test fitting and verify manifold pres sure reads 3 5 inches water column 0 87 kPa for natural gas and 10 0 inches water...

Page 32: ...it Remove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and red spring for propane g...

Reviews: