background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

15

Outside combustion air ducting may be run
upwards or vertically through framing and ceil-
ing joists, with the hood installed through an
outside wall and 3' (914 mm) below the termi-
nation. Ducting may also be run downward
through floor joists and under the home to a
ventilated crawlspace not considered part of
the living area of the home.

Note: Do not terminate combustion air kit in
attic space under any circumstances.

FTF10-TMS Termination Shroud

An optional termination shroud is available to
partially conceal the FTF10-CTDTM when in-
stalled on a chase. Model FTF10-TMS is adjust-
able for chases measuring a minimum of 27" x
27" (686 mm x 686 mm) up to a maximum of
40 

¹⁄₂

" x 40 

¹⁄₂

" (1029 mm x 1029 mm). Consult

the FTF10-TMS installation instruction for spe-
cific installation information.

Glass Doors

If glass doors are to be installed on these
fireplaces, refer to specific installation instruc-
tions packed with the glass doors. Use only the
doors that are listed for use with these fire-
places. Use of other non-listed glass door on
these fireplaces may constitute a potential fire
hazard and is not recommended.

CAUTION: CERTAIN GLASS DOORS OVER-
LAP THE BLACK METAL FACING OF THE FIRE-
PLACE. IF THE FIREPLACE HAS BEEN FACED
WITH NONCOMBUSTIBLE MATERIALS,
THERE MIGHT NOT BE SUFFICIENT CLEAR-
ANCE TO INSTALL THE GLASS DOORS OF
YOUR CHOICE. ENSURE ADEQUATE CLEAR-
ANCE IS MAINTAINED AT ALL TIMES SO AS
NOT TO INTERFERE WITH THE INSTALLA-
TION AND OPERATION OF GLASS DOORS.

GAS LINE CONNECTION

The Colonial Series fireplaces have been ap-
proved to accept a 

¹⁄₂

" (13 mm) gas line for an

approved gas appliance. Always have the appli-
ance installed by a qualified, licensed plumber
in accordance with all local building codes. The
gas line may enter either side of the fireplace.

CAUTION: PLUMBING CONNECTIONS SHOULD
ONLY BE PERFORMED BY A QUALIFIED, LI-
CENSED PLUMBER. MAIN GAS SUPPLY MUST
BE OFF WHEN PLUMBING GAS LINE TO FIRE-
PLACE OR PERFORMING SERVICE.

If you’re installing a gas line, connect it before the
fireplace is framed and enclosed in the finished
wall. The gas knockout is determined by a 1 

¹⁄₈

"

(29 mm) round indentation located at the bottom
and slightly off center in the side refractories.

THE KNOCKOUT IS ALWAYS REMOVED FROM
INSIDE THE FIREPLACE. DO NOT REMOVE THE
KNOCKOUT UNLESS YOU ARE INSTALLING A
GAS LINE. 
If removal is attempted from the outer
wrapper, side-refractory damage may occur.
With a medium-sized hammer, lightly tap the
surface of the indentation. The refractory mate-
rial is very thin in this area and is easily removed.
Once a small hole has been made, continue
tapping until you have reached sufficient diam-
eter for the gas line to fit through. The entire
knockout does not have to be removed. Remove
insulation in the gas line channel.

Install a 

¹⁄₂

" (13 mm) gas supply line through

fireplace wall for connection to a decorative gas
appliance inside the firebox. Outside, the gas
supply line connects to a gas shut-off valve
recessed flush into the wall or floor. The valve
should be controlled by a removable valve key
for safety.

Always plumb gas line installation per local
codes. Check all connections with soap suds;
leaks will bubble. Never test any gas line con-
nection with a match or open flame.

IMPORTANT: RE-PACK INSULATION MATE-
RIAL IN SQUARE HOLE AROUND GAS LINE;
INTERIOR AND EXTERIOR, TO SEAL.

This provision is intended only for connection
to a decorative gas appliance incorporating an
automatic shut-off device and complying with
the standard for Decorative Gas Appliances for
installation in vented fireplaces, ANSI Z21.60.
Install in accordance with the National Fuel Gas
Code, ANSI Z223.1. This complies with the
revised U.L. 127 standard.

CAUTION: WHEN USING THE DECORATIVE
GAS APPLIANCE, THE FIREPLACE DAMPER
MUST BE SET IN THE FULLY OPEN POSITION.

Vent Free Appliances

These units have been tested and approved to
ANSI/IAS/AGA Z21.11.2 for use with unvented
gas appliances and complies with the stan-
dard for Factory-Built fireplaces, UL 127.

The unit has been tested for use with any
unvented gas log sets having a maximum rating
of 40,000 BTU.  The minimum mantle configu-
rations are outlined in 

Figures 45 and 46.

These fireplaces have been marked with a
maximum rating of 40,000 BTU to assure that
homeowners do not exceed the allowable lim-
its for all allowed installations of mantles.

NEVER INSTALL AN UNVENTED GAS LOG
SET WITH A BTU GREATER THAN 40,000.

COLD CLIMATE INSULATION

If you live in a cold climate, it is especially
important to seal all cracks around the fireplace
opening with noncombustible material and
wherever cold air could enter the room. Sur-
rounding materials must be caulked where it
meets the black metal facing of the fireplace to
avoid cold air intrusion. Use noncombustible
caulking material only on fireplace facing to
seal. Also, the outside air inlet duct should be
wrapped with noncombustible insulation to
minimize the formation of condensation. Do
not place insulation materials against chimney
sections.

Note: A 2" (51 mm) air space must be preserved
for all combustible materials extending for any
continuous length adjacent to the chimney.

It is especially important to insulate between
the studs of an outside chase cavity and under
the floor if the floor is above ground level. Do
not place insulation directly against the fire-
place or chimney system

FIREPLACE FINISHES
Mantels and Trim

In Canada, the minimum height for a combus-
tible mantel is 24" (610 mm) above the fire-
place opening. 

Figure 45 shows typical Cana-

dian installation. In installations other than
Canada, combustible mantels and trim may be
installed 12" (305 mm) above the fireplace
opening as per NFPA 211; Section 7-2.3.3. and
Figure 46. If a mantel is of a noncombustible
material, it is exempt from these requirements
as long as it does not interfere with the instal-
lation or operation of glass doors.

Combustible

Mantel

Spacer

Noncombustible

Wall Covering

Finished

Wall

Canadian Installation

Fireplace

Opening

Facing

Flush

24" Min.

(610mm)

8" Max.

(203mm)

Figure 45

Summary of Contents for COLONIAL COL-3629

Page 1: ...nstructions before beginning your installation Do not alter or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not l...

Page 2: ...ur distributor or qualified factory representative to ensure safe condition When in doubt con sult your distributor 16 For additional safety considerations and complete operating instructions refer to...

Page 3: ...llationinresidentialhomesandbuildingsof conventionalconstruction notinmobilehomes These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for ch...

Page 4: ...n Note Non Combustible Chase Flashing Must be Used to Cover Chase Opening Optional Insulation in Outside Walls of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 2 4m Level He...

Page 5: ...ng Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney and surround ma terials such as brick stone...

Page 6: ...THEM Step 4 Fireplace may be anchored to floor Bend down four 4 anchor tabs located at the base of the fireplace and secure to the floor by nailing with 8d nails Figure 10 Note The Z type safety stri...

Page 7: ...7 445 mm K 67 1702 mm Framing Dimensions Figure 16 Flue Type A B FTF10 19 19 Vertical 483 mm 483 mm FTF10 30 19 29 Offset 483 mm 737 mm Framing Dimensions for Ceiling Figure 14 Figure 15 Pitch C D 0 1...

Page 8: ...ward Ensure nothing blocks the hood opening This air duct must never terminate higher than the chimney Step 9 Cut or frame hole through the outside wall for the installation of the duct inlet hood A 4...

Page 9: ...tenoughtopen etrate the roof flashing openings Figure 26 Always maintain 2 minimum air space to com bustiblematerialsandalwayscheckeachchim ney joint inner and outer to ensure proper engagement Checkv...

Page 10: ...ntative paint designed for metal This is especially important when installationsaremadeinabnormallyadverseor corrosive environments such as near lakes oceans or in areas with consistently high hu midi...

Page 11: ...sfromtotaldesiredheight Reference Vertical Elevation Chart and deter minethenumberofchimneysections quantity and length required SPECIAL OFFSET INSTRUCTIONS To clear any overhead obstructions you may...

Page 12: ...3 Use Elevation Chart as job estimator only Add necessary firestop spacers and sta bilizers as required Firestop spacers must be used as shown in Figures 21 and 22 and stabilizers as shown in Figure...

Page 13: ...171 14 3 0 0 5 182 15 2 1 0 5 188 15 8 0 1 5 192 16 0 2 0 5 198 16 6 1 1 5 206 17 2 0 0 6 215 17 11 1 0 6 222 18 6 0 1 6 226 18 10 2 0 6 232 19 4 1 1 6 240 20 0 0 0 7 250 20 10 1 0 7 256 21 4 0 1 7 FT...

Page 14: ...s install the same way as round terminations and stabilizers Step 1 Hold return elbow over top of last chimney section Step 2 Center inner slip section into inner flue pipe slip down Step3 Centerouter...

Page 15: ...line connects to a gas shut off valve recessed flush into the wall or floor The valve should be controlled by a removable valve key for safety Always plumb gas line installation per local codes Check...

Page 16: ...BTU IN FT2 HR F At no time may a perpendicular side wall be located closer than 9 from the fireplace opening If fireplace is installed diagonally across a 90 corner no wall shields are required Figure...

Page 17: ...4 2 3 4 Cultered Stone Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111...

Page 18: ...er any problems or have ques tions concerning the installation or application of this system please contact your distributor For the name of your nearest distributor call LENNOX HEARTH PRODUCTS 1110 W...

Page 19: ...2 Firestop Spacer Flat 63L36 F10FS 2 Chase Termination Square 63L52 FTF10 CT2RS INSTALLATION COMPONENTS Firestop Spacer 30 63L37 F10FS30 2 Round Termination 63L55 FTF10 CTDTM Termination Shroud 63L56...

Page 20: ...at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A...

Reviews: