background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

 Input (BTU/HR) Manually-Modulated Gas 

Valves (millivolt models)

Model

NATURAL GAS

(BTU / HR)

PROPANE GAS 

(BTU / HR)

ADAGIO-MN

1,000 high

10,000 low

-------------

ADAGIO-MP

-------------

1,000 high

10,000 low

Table 1

 Input (BTU/HR) Electronic Models 

Model

NATURAL GAS

(BTU / HR)

PROPANE GAS 

(BTU / HR)

ADAGIO-EN

1,000 high

10,000 low

-------------

ADAGIO-EP

if field converted

-------------

1,000 high

10,000 low

Table 2

Burner Orifice Sizes 

Elevation 0-4500 feet ( 0-172 meters)

Model

Series

Nat.Gas

drill size (inches)

Propane

drill size (inches)

ADAGIO-MN

#51

-------------

ADAGIO-MP

-------------

#58

ADAGIO-EN

#51

-------------

ADAGIO-EP

if field converted

-------------

#58

Table 5

Electronic Models - 

Electronic models have a manually modulated 

gas valve.  Input of electronic models is shown 

in the following table:

These appliances are designed to operate on 

natural or propane gas only. The use of other 

fuels  or  combination  of  fuels  will  degrade 

the performance of this system and may be 

dangerous.

Millivolt Models - 

Millivolt models come standard with the manu-

ally-modulated gas valve; flame appearance and 

heat output can be controlled at the gas valve.
Input of millivolt models is shown in the fol-

lowing table:

Gas Pressure - All Models 

Tables 3 and 4

 show the appliances' inlet and 

manifold gas pressure.

Inlet Gas Supply Pressure 

(all models)

Fuel #

Minimum

Maximum

Natural Gas

5.0" WC

(1.24 kPa)

10.5" WC

(2.61 kPa)

Propane

11.0" WC

(2.74 kPa)

1.0" WC

(.2 kPa)

Table  3

Manifold Gas Supply Pressure

(all models)

Fuel #

Low

High

Natural 

Gas

(Lo) 2.2" WC

(.55 kPa)

(Hi) .5" WC

(.87 kPa)

Propane (Lo) 6." WC

(1.57 kPa)

(Hi) 10.0" WC

(2.49 kPa)

Table  4

Test gauge  connections  are  provided  on  the 

front of the millivolt and electronic gas control 

valve (identified IN for the inlet and OUT for 

the manifold side). The control valves have a 

3/8" (10 mm) NPT thread inlet and outlet side 

of the valve.

These appliances must be isolated from the 

gas supply piping system (by closing their 

individual manual shut-off valve) during any 

pressure  testing  of  the  gas  supply  piping 

system  at  test  pressures  equal  to  or 

less 

than

 1/2 psig (3.5 kPa).

These appliances and their individual shut-off 

valves must be disconnected from the gas 

supply piping system during any pressure 

testing of that system at pressures 

greater 

than

 1/2 psig (3.5 kPa).

Orifice Sizes - Sea Level To High Altitude

(All Models)

These appliances are tested and approved for 

installation at elevations of 0-4500 feet (0-1372 

meters)  above  sea  level,  using  the  standard 

burner orifice (See 

Table 5)

.  For elevations 

above  4500  feet,  contact  your  gas  supplier 

or  qualified  service  technician.    Install  the 

appliance according to the regulations of the 

local authorities having jurisdiction and, in the 

USA,  the  National  Fuel  Gas  Code  NFPA  54  / 

ANSI Z223.1 - latest edition or , in Canada, the 

CAN1-B149.1 and .2 codes - latest edition.

Table  5

  shows the gas orifice size required 

for the elevations indicated.

       WARNING 

Propane  tanks  are  at  pressures 

that will cause damage to valve 

components.  Verify  that  the 

tanks have step down regulators 

to  reduce  the  pressure  to  safe  

levels.

The millivolt appliances are manually controlled 

and feature a spark igniter (piezo) that allows the 

appliance's pilot gas to be lit without the use of 

matches or batteries.  This system provides con-

tinued service in the event of a power outage.

Do  not  use  these  appliances  if  any  part  has 

been under water.  Immediately call a qualified, 

professional service technician to inspect the 

appliance and to replace any parts of the control 

system and any gas control which have been 

under water.

Ne pas se servir de cet appareil s'il a été plongé 

dans l'eau, complètement ou en partie.  Appeler 

un technicien qualifié pour inspecter l'appareil et 

remplacer toute partie du système de contrôle 

et toute commande qui ont été plongés dans 

l'eau.

This appliance is only for use with the type 

of  gas  indicated  on  the  rating  plate.  This 

appliance  is  not  convertible  for  use  with 

other  gases,  unless  a  certified  kit  is  used.

Cet  appareil  doit  être  utilisé  uniquement 

avec les types de gaz indiqués sur la plaque 

signalétique.  Ne pas l'utiliser avec d'autres 

gaz sauf si un kit de conversion certifié est 

installé.

These appliances must not be connected to a 

chimney or flue serving a separate solid fuel 

burning appliance.

Carbon Monoxide Poisoning: Early signs of 

carbon monoxide poisoning are similar to the 

flu with headaches, dizziness and/or nausea. 

If you have these signs, obtain fresh air im-

mediately. Have the appliance serviced by a 

qualified technician as it may not be operating 

correctly.  Some people are more affected by 

carbon monoxide than others.  These include 

pregnant women, people with heart or lung 

disease or anemia, those under the influence 

of alcohol, and those at high altitudes.

Summary of Contents for Adagio ADAGIO-EN

Page 1: ...rating plate This appliance is not convertible for use with other gases unless a certified kit is used Adagio Series US P N 850 044M Rev D 06 2008 In the Commonwealth of Massachusetts Installation must be performed by a licensed plumber or gas fitter See Table of Contents for location of additional Commonwealth of Massachusetts requirements Millivolt Models Electronic Model ADAGIO MN ADAGIO EN ADA...

Page 2: ...iances Millivolt appliances are designed to operate on natural or propane gas A millivolt gas control valve with piezo ignition system provides safe efficient operation External electrical power is required to operate the optional blower if installed in these units Electronicappliancesaredesignedtooperateon natural or propane gas An electronic intermit tent pilot ignition system provides safe effi...

Page 3: ...ea Level To High Altitude All Models These appliances are tested and approved for installationatelevationsof0 4500feet 0 1372 meters above sea level using the standard burner orifice See Table 5 For elevations above 4500 feet contact your gas supplier or qualified service technician Install the appliance according to the regulations of the local authorities having jurisdiction and in the USA the N...

Page 4: ...or with an alarm shall be installed Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet abovegradedirectlyinlinewithth...

Page 5: ...2 1 latest edition MANUFACTURED HOME REQUIREMENTS This appliance may be installed in an after market permanently located manufactured home USA only or mobile home where not prohibited by local codes Cet appareil peut être installé dans un maison préfabriquée É U seulement ou mobile déjà installée à demeure si les réglements locaux le permettent Manufactured Home installations must be installed in ...

Page 6: ... Degree Elbow Secure Vent Secure Flex flex elbow 52 1321 53 3 4 1365 Includes 4 clearance to combustibles required above vent components MINIMUM CLEARANCES Inches millimeters Back 1 2 in 13 mm Sides 1 2 in 13 mm Top Spacers 0 in 0 mm Floor 0 in 0 mm FromBottomofUnit To Ceiling 64 in 1626 mm Vent 3 76 Top 1 25 4 Sides Bottom SERVICE CLEARANCES Feet meters Front 3 feet 0 9 meters Table 6 Do not insu...

Page 7: ... 91 cm 3 feet 91 cm J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15 2 cm for appliances 10 000 BTU hr 3kW 12 in 30 cm for appliances 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 inches 91 cm for appliances 100 000 BTU hr 30kW 6 in 15 2 cm for appliances 10 000 BTU hr 3kW 9 in 23 cm for appliances 10 000 BTU hr 3kW and 50 000BTU ...

Page 8: ... according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Horizontal Vent Termination Clearances The horizontal vent termination must have a minimum of 3 76 mm clearance to any overhead combustible projection of 2 1 2 64 mm or less See Figure 7 For projections exceeding 2 1 2 64 mm see Figu...

Page 9: ...ed in Figure 9 unless the appliance is to be installed in a corner See Figure 10 for corner framing installations All framing details must allow for a minimum clearance to combustible framing members as shown in Table 6 on Page 6 If the appliance is to be elevated above floor level a solid continuous platform must be constructed Headers may be in direct contact with the appliance top spacers but m...

Page 10: ...2 191 Outer 36 23 32 933 21 1 16 535 1 7 8 48 6 1 16 154 8 7 32 209 1 1 2 38 15 1 32 382 15 15 32 393 7 11 16 195 34 864 40 1 32 1017 20 3 4 527 14 3 4 375 5 13 32 137 Due to Lennox ongoing commitment to quality all specifications ratings and dimensions are subject to change without notice Figure 11A FIREPLACE specifications ...

Page 11: ...ice With the facade installed required sold separately the appliance base will need to be elevated a minimum of 3 4 above the floor to allow for the proper fit of the facade i e use 3 4 board minimum as platform Figure 11B FACADE specifications Facade Required arched style shown 26 3 4 680 38 1 2 978 20 1 4 514 14 13 16 376 1 2 13 1 2 13mm 1 1 2 38mm Arch Facades Black and Brushed Nickel Finishes ...

Page 12: ...cation The following sections describe vertical roof and horizontal exterior wall vent applications Refer to the section relating to your installation A list of approved venting components are shown in the tables on Page 30 Vertical Termination Systems Roof Figures 17 and 23 through 25 on Pages 14 and 16 and their associated Vertical VentTablesillustratethevariousverticalventing configurations tha...

Page 13: ...1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2 0 1 5 8 2 0 0 0 2 4 5 3 0 1 5 2 6 8 0 0 0 3 0 3 8 0 1 9 1 0 0 3 0 4 4 1 1 5 9 0 2 0 0 2 4 7 ...

Page 14: ...gthedimplesdown and along the incline channels until they seat at the end of the channels This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 16 D Install firestop spacer at ceiling When usingSecureVent useSV4 5VFfirestop spacer at ceiling joists when using Secure Flex use SF4 5VF firestop spacer If there is living space above the ceiling level the firest...

Page 15: ...Page 7 The SV4 5CGV 1 Vertical Termination Figure 22 installs in the exact same fashion as any other Secure Vent section Align the termination over the end of the previously installed section adjusting the radial alignment until the four locking dimples of the termination are aligned with the inlets of thefourinclinechannelsofthelastventsection Pushtheterminationdownuntilitfullyengages thentwistth...

Page 16: ...acer SF4 5VF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF WARNING UnderNoCircumstances MaySepa rate Sections of Concentric Flexible Vent Pipe Be Joined Together V H1 H V1 uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF Example If ...

Page 17: ...on lengths are available Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists Make allowances for elbows as indicated in Figure 18 on Page 14 Maintain a minimum 1 25 mm clearance to combustibles on the vertical sections Clear ances for the horizontal runs are 3 76 mm on top 1 25 mm on sides and 1 25 mm at the bottom B Frame exterior wall opening Locate...

Page 18: ...m at all sides for all vertical runs and 3 76 mm at the top 1 25 mm at sides and 1 25 mm at the bottom for all horizontal inclined runs J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as describedinStepB Assembletheventsystem to point where the terminus of the last section is within 6 in 152 mm to 9 1 4 in 235 mm...

Page 19: ... show a 1 V to 5 H ratio up to a maximum horizontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system see Figure 29 AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 See Table 7 as an aid in venting component selection for a particular range of exterior wall thickne...

Page 20: ...al run of 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 29 V H H1 V1 Wall Firestop Spacer SV4 5HF Ceiling Firestop Spacer SV4 5VF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF Example If 20 feet total H H1 horizontal vent run...

Page 21: ...vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1 3 4 inches from the end and that it is free...

Page 22: ...ure 11A on Page 10 3 Remove the cover plate s knockout and then feedthepowersupplywirethroughtheknock out opening and into the unit junction box 4 Connect the black power supply wire to the red pigtail lead and the white power supply wire to the common terminal of the outlet as shown in Figures 36 and 37 5 Connect the ground supply wire to the pig tail lead attached to outlet s green ground screw ...

Page 23: ...by striking or slamming it Handle this glass with extreme care Glass is susceptible to damage Do not scratch or handle roughly while reinstalling the glass door frame BLOWER CONTROL CIRCUIT WIRING 120V 60HZ 1PH Factory Wired Ground Field Wired Junction Box Tab Intact Tab Broken Plug blower into this receptacle n e e r G d n u o r G Wall mounted ON OFF Blower Switch or Variable Speed Control Switch...

Page 24: ...k for leaks Turn on gas supply and test for gas leaks using a gas leak test solution also referred to as bubble leaksolution Note Usingasoapywatersolution 50 dish soap 50 water is an effective leak test solution but it is not recommended because the soap residue that is left on the pipes fittings can result in corrosion over time Gas Valve 3 8 NPT x Flare Fitting 3 8 Flex Tubing 3 8 Nipple 3 8 Uni...

Page 25: ...enter to provide a natural fire look WARNING DO NOT attempt to install the logs until the appliance installation has been completed the gas line connected and tested for leaks and the initial burner operation has been checked out Logs get very hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Turn off all electricity to the appliance before you in...

Page 26: ...ion the hole on the bottom of log D over pin 3 4 Place the right front log E as shown in Figure 45 Position the hole on the bottom of log E over pins 4 and 5 6 Ember Placement Separate the Embers rockwool into pieces about the size of a quarter see Figure 41 Keep the pieces fluffed up not matted Distribute these pieces over the surface of the burner as shown in Figure 47 Do not use more than is ne...

Page 27: ... Nozzels Figure 49 Figure 48 MILLIVOLT Thermocouple Hood Igniter Rod 3 8 Min 9 mm Thermopile Pilot Nozzels Step 10 Checking Appliance Opera tion With gas line installed run initial system check outbeforeclosingupthefrontoftheunit Follow the pilot lighting instructions provided in the Care and Operation Manual For piezo igniter location see Figure 39 on Page 24 millivolt appliances only Note Lighti...

Page 28: ... switch in the OFF position Close the lower control compartment panel Note See Figure 50 for proper burner flame appearance Air Shutter Adjustment Guidelines If there is smoke or soot present first check the log set positioning to ensure that the flames are not impinging on any of the logs If the log set is properly positioned and a sooting condition still exists then the air shutter opening shoul...

Page 29: ...ion Ahearthextensionisnotrequiredwiththisappliance Ifahearthextension is used do not block the lower control compartment panel Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements Note Combustible wall finish materials and or surround materials must not be allowed to encroach the area defined by the appliance front fac...

Page 30: ...nt Sections ListedSecureVentComponents Cat No Model Description These termination kits include firestop spacer gear clamps and flex adapter H1969 SF4 5HT 2 HorizontalSquareTermina tion withoutflex 77L87 SFKIT12S FlexSquareTerm with 12inch 305mm compressedflex 77L88 SFKIT18S FlexSquareTerm with 18inch 457mm compressedflex 77L89 SFKIT24S FlexSquareTerm with 24inch 610mm compressedflex 77L90 SFKIT36S...

Page 31: ...nsdufabricantettoutesexigences et codes applicables de l autorisés avoir la juridiction Si l information danscetteinstructionn estpassuivie exactement unfeu explosionoupro ductiondeprotoxydedecarbonepeut résulterledommagescauserdepro priété perteoublessurepersonnelle devie L agencequalifiéedeservice estesponsabledel installationpropre de cet équipment L installation n est pas propre et compléte ju...

Page 32: ...e orifice B Retrieve the burner and slide the venturi tube over the orifice see Figure 53 Set the burner assembly into its position and secure it Figure 56 Burner Orifice Step8 Reassembletheremainingcomponents by reversing the procedures outlined in the preceding steps Use pipe joint compound or Teflon tape on all pipe fittings before installing ensurepropaneresistantcompoundsareused in propane ap...

Reviews: