M3000 Installation Guide
79
CHAPTER 7
Pre-Power Up Testing
Follow the steps below before powering up the controller.
1.
Measure the AC power supplied to the power supply (110 VAC or 220 VAC, depending on the
power supply installed). The power supply must have a dedicated circuit breaker. Do
not
plug
into an outlet that is controlled by an on/off switch.
2.
Test the reader power wiring to determine if a short circuit exists. Unplug each reader connector
and measure, from the reader connector going out to the readers between pin 1 to chassis and
pin 1 to pin 2, with an ohmmeter.
Result
: A measurement of less than 100 ohms indicates a short circuit. Correct this condition
before powering up.
3.
If a 16DO board is installed, check for a short circuit. Unplug each connector and measure from
chassis ground to all pins on the DO connector.
Result
: A measurement of less than 100 ohms indicates a short circuit. Trace out the wiring to
locate the short circuit.
4.
Reconnect all connectors.
5.
Disconnect power input connector J6 on the Power/Communications board.
6.
Use a voltmeter to measure input voltage across J6. Pin 3 = +, pin 4 = Ground.
Result
: If the meter reads -12 to -15 VDC, the wires are reversed.
Solution
: Reverse the wires on pins 3 and 4 so pin 3 is the + voltage. The meter should read +12
to +15 VDC.
7.
Reconnect the J6 connector.
Once you have completed these steps, power up the M3000.
Summary of Contents for m3000
Page 1: ...7 3 M3000 Installation Guide...
Page 4: ......
Page 14: ...Introduction 14 M3000 Installation Guide...
Page 30: ...Power Communications Board 30 M3000 Installation Guide...
Page 32: ...PXNplus CPU Board 32 M3000 Installation Guide PXNplus CPU Board Layout...
Page 38: ...Reader Processing Boards 38 M3000 Installation Guide 2RP Board Layout 2RP Board Layout...
Page 50: ...Reader Processing Boards 50 M3000 Installation Guide 2SRP Board Layout 2SRP Board Layout...
Page 55: ...M3000 Installation Guide 55 2SRP Board 2SRP Supervised Reader Connector Points...
Page 61: ...M3000 Installation Guide 61 2SRP Board Wiring 2SRP Door Strike Internal Relay...
Page 65: ...M3000 Installation Guide 65 8RP Board Board Layout 8RP Board Layout...
Page 70: ...Reader Processing Boards 70 M3000 Installation Guide...
Page 72: ...Optional DI and DO Boards 72 M3000 Installation Guide 20DI Board Layout 20DI Board Layout...
Page 75: ...M3000 Installation Guide 75 16DO and 16DOR Boards 16DO Board Layout...
Page 76: ...Optional DI and DO Boards 76 M3000 Installation Guide 16DOR Board Layout...
Page 80: ...Pre Power Up Testing 80 M3000 Installation Guide...
Page 99: ...M3000 Installation Guide 99 CE Regulatory Notice CE Regulatory Notice...
Page 100: ...Regulatory Information 100 M3000 Installation Guide...
Page 110: ...110 M3000 Installation Guide...
Page 114: ...114 M3000 Installation Guide Resistances Detected by PXNplus...
Page 117: ...M3000 Installation Guide 117 Index...