DirecDoor Installation Guide
81
UL Compliance
•
The DirecDoor is not intended to be installed as a stand-alone unit as neither it nor the
compatible UL Listed Altronix Corp. Model AL300ULM power supply does not incorporate a
designated AC power-on indicator visible after installation.
•
PSDN (Ethernet) communication between the premise unit and monitoring station equipment
must be primary and DACT (telco) communication secondary in UL installations.
UL Approved System Configuration
•
The DirecDoor access panel is UL Listed as an access control unit and a proprietary burglar
alarm control unit (UL 1076 and UL 294). The DirecDoor access panel should be used with the
listed OnGuard system.
•
The power supply’s AC power fail contacts must be wired to the DirecDoor as shown in figure
Wiring Auxiliary Power Supply with Built-in Relay for Fault Output (AC Power Fail)
•
Grounding must be in accordance with Article 250 of the National Electrical Code.
•
The DirecDoor must be used with listed card readers.
•
The exit request input circuit and initiating device must be contained within the secured area. The
exit device circuit must be connected to listed switches or exit devices.
•
The DirecDoor must be mounted inside the secured area.
•
The door strike power must be provided from a listed burglar alarm system power supply. If the
door strike circuit is arranged as fail secure (door remains locked upon loss of power), listed
emergency panic hardware must be provided to allow exit from the secured area. A fail-safe
configuration results in the door strike circuit unlocking in case of a power loss.
•
The number of separate signals on a single channel shall be limited to 1000.
•
The DirecDoor tamper switch must be wired to the Power/Communications board as shown in
figure
Wiring Auxiliary Power Supply with Built-in Relay for Fault Output (AC Power Fail)
.
•
Alarms in OnGuard should be set using the following priority list with 1 being the highest
priority and 7 being the lowest:
–
Fire alarm and industrial supervision
–
Hold-up or panic alarm
–
Burglar alarm
Summary of Contents for DirecDoor
Page 1: ...7 4 DirecDoor Installation Guide...
Page 4: ......
Page 8: ...Table of Contents 8 DirecDoor Installation Guide...
Page 14: ...Introduction 14 DirecDoor Installation Guide...
Page 19: ...DirecDoor Installation Guide 19 Mounting DirecDoor Mounting Template...
Page 22: ...Installation Planning and Mounting 22 DirecDoor Installation Guide...
Page 56: ...DDIO Interface 56 DirecDoor Installation Guide Resistances Detected by PXNplus...
Page 58: ...DO Interface 58 DirecDoor Installation Guide Wiring Output Device to DO Interface...
Page 76: ...Controller Firmware Tools 76 DirecDoor Installation Guide...
Page 79: ...DirecDoor Installation Guide 79 CE Regulatory Notice CE Regulatory Notice...