DirecDoor Installation Guide
37
CHAPTER 5
Reader Interface
The DirecDoor reader interface provides:
•
four (4) supervised Device Inputs (DI)
–
two (2) alarm DIs and
–
two (2) exit DIs,
•
two (2) reader LED outputs, and
•
two (2) door strike DO relays.
Note:
The DDSDC supports only one door strike DO relay, one alarm DI, and one exit DI on
Connector J2.
The reader voltage is 12 VDC only.
The reader interface is limited to only one type of reader technology:
•
Wiegand,
•
F/2F, or
•
Supervised F/2F.
The reader interface has built-in pull-up resistors to accommodate cable lengths over 500 feet
(152.40 m). External pull-up resistors are not required for the reader interface.
In Supervised F/2F mode, the DI (alarm point) is available at the reader or at the controller on
Supervised F/2F readers that support DIs and Exit DIs.
Setting the DIP Switches
Set DIP switches as described in the tables below before installing and wiring readers.
Reader Technology (SW1-1 through SW1-4)
Reader Technology
SW1-1
SW1-2
SW1-3
SW1-4
Not Valid
Summary of Contents for DirecDoor
Page 1: ...7 4 DirecDoor Installation Guide...
Page 4: ......
Page 8: ...Table of Contents 8 DirecDoor Installation Guide...
Page 14: ...Introduction 14 DirecDoor Installation Guide...
Page 19: ...DirecDoor Installation Guide 19 Mounting DirecDoor Mounting Template...
Page 22: ...Installation Planning and Mounting 22 DirecDoor Installation Guide...
Page 56: ...DDIO Interface 56 DirecDoor Installation Guide Resistances Detected by PXNplus...
Page 58: ...DO Interface 58 DirecDoor Installation Guide Wiring Output Device to DO Interface...
Page 76: ...Controller Firmware Tools 76 DirecDoor Installation Guide...
Page 79: ...DirecDoor Installation Guide 79 CE Regulatory Notice CE Regulatory Notice...