26
E-Flex User Manual, Rev. 1.30
Load setup
Set Load Type
Press
Menu,
inpX
menu is displayed.
Press the
Down
button three times to scroll to the
load
menu.
Press
Enter
to display the
zone select
menu.
Use the
Up
and
Down
buttons to select a zone to setup.
Press
Enter
, the
type
list control is displayed.
Press
Enter
, the current programmed type option will be displayed first.
Use the
Up
and
Down
buttons to display the available options:
Opt1
– 0-10V dimming (default)
Opt2
- Switched
Opt3
– Receptacle*
Press
Sel
to choose the displayed option. The apostrophe LED will be lit for the current programmed
option. Press
Store button
to record the new setting.
*receptacle type ignores daylight sensor input, also high and low end trim.
Set Low End Trim and relay cutoff
Press
Menu,
inpX
menu is displayed.
Press the
Down
button three times to scroll to the
load
menu.
Press
Enter
to display the
zone select
menu.
Use the
Up
and
Down
buttons to select a zone to setup.
Press
Enter
, the
type
list control is displayed.
Press the
Up
button to scroll to the
trim
menu.
Press
Enter
, the
low end
entry control is displayed.
Press
Enter.
The current value will be displayed.
Use the
Up
and
Down
buttons to set the trim between 0 and 45%. The default
is 1%. Press
Store
button to record the new setting.
Note: low end trim is used as the relay cutoff threshold. For switched load type it sets minimum light
level and load switches when control is > lo trim. To turn off switched load set lo trim to zero.