background image

Wattstopper

 

®

High Bay • Line Voltage • Passive Infrared
IP65 Occupancy Sensors for Wet Locations

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24140 – 08/17  rev. 2

Catalog Numbers • Les Numéros de Catalogue • Los Números de Catálogo: HB330W, HB340W, HB350W  

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

1.  Review the ADJUSTMENTS section and complete any 

necessary DIP switch setting changes. 

2.  Mount the sensor so the lens is below the edge of the fixture 

and away from the lamps. Heat from the lamps could affect 

the sensor operation. 

Make sure that you have the appropriate accessories for the sensor mounting 

configuration. (See Mounting Options.)

3.  Assemble any necessary mounting accessories and attach them to the sensor 

module. Make sure that the flying leads from the sensor module cable are 

accessible inside the fixture. 

4.  Connect the line voltage and load wires to the sensor leads as shown in the 

applicable Wiring Diagram for the sensor module.
•  Do not allow bare wire to show. 
•  Make sure all connections are secure.
•  Check all gaskets for watertight fit.

5.  Check sensor operation. Refer to the TESTING section.

6.  Attach the Lens to the HB3x0W as shown in the sensor assembly drawing.

DESCRIPTION AND OPERATION

The HB3x0W occupancy sensors are designed for automatic lighting control in high bay wet location applications. The HB3x0W sensors 

contain a passive infrared sensor (PIR). The sensors are modular and are made up of two parts, a Sensor Module (HB3x0W) and a 

Lens (HBLxW).

The sensor module is available in three models for different line voltage applications: HB350W for 120/277VAC, HB340W for 

347/480VAC, and HB330W for 208/240VAC. 

The sensors use a set of DIP switches to set the time delay and PIR sensitivity as explained on page 3. The HB350W provides a single 

load controlling relay. The HB330W and HB340W have two relays for phase switching.

SPECIFICATIONS

HB350W Voltages ..............................................................Voltages120/277VAC,60Hz
 

Load Requirements

 

@120VAC, 60Hz ........................................................0-800W ballast or tungsten

 

@277VAC, 60Hz .........................................................................0-1200W ballast

 @120VAC ...................................................................................................1/6 hp
HB340W Voltages .......................................................................... 347/480VAC, 60Hz
 

Load requirements ......................................................................0-1200W ballast

HB330W Voltages .......................................................................... 208/240VAC, 60Hz
 

Load requirements ......................................................................0-1200W ballast

Wiring cable ....................................3 or 4-conductor 18AWG stranded, UL Style 2517
Unit Dimensions .................................................................. 4.08” diameter, 1.88” thick
Threaded nipple ........0.81” diameter, 0.40” long fits standard 1/2” electrical conduit fitting
Weight ............................................................................................0.28 lb (130 grams)
Material .........................................................ABS, UL94-5VA flame retardant material,
 

 ................. UV resistant, indoor use only, minimum plastic wall thickness 2.5mm

Environment ......................................................................................... IP65 Compliant
Operating temperature ................................................. -40°F (-40°C) to 131° F (55°C)
Storage temperature ..................................................... -40°F (-40°C) to 176°F (80°C)
Operating humidity ........................................................5 to 95% RH, non-condensing
Maximum Dew Point  .................................................................................29°C (85°F)
US Patents: ........................................................................... 5,640,113 and 5,804,991

INSTALLATION OVERVIEW

CAUTION

TURN THE POWER OFF AT THE  

CIRCUIT BREAKER BEFORE INSTALLING THE SENSOR.

HB3x0W (sensor module)

HBLxW (lens module)

L7 lens may require pliers 

to remove the lens. (Grab 

one of the fins to remove.)

Tightening ring

Sensor Assembly

DIP switches

HB3x0W L2W/

HB3x0W L3W

HB3x0W L7W

Summary of Contents for Wattstopper HB330W

Page 1: ...passive infrared sensor PIR The sensors are modular and are made up of two parts a Sensor Module HB3x0W and a Lens HBLxW The sensor module is available in three models for different line voltage applications HB350W for 120 277VAC HB340W for 347 480VAC and HB330W for 208 240VAC The sensors use a set of DIP switches to set the time delay and PIR sensitivity as explained on page 3 The HB350W provides...

Page 2: ...ncy control feature of the HB3x0W sensor module When occupancy control is disabled the load remains ON as long as the sensor is powered Switch 8 Load Effect OFF Controlled by Occupancy ON PIR override Load always ON Wet location light fixture supplied by others HB3xxW sensor HBEM3W Extender housing Chase nipple Threaded nut Rubber washer Wet location light fixture supplied by others Threaded femal...

Page 3: ...otion plus the Time Delay If no occupancy is detected during the 60 second start up the load may come on anyway during the start up If no occupancy is detected by the time the start up is complete the relay opens and the load turns OFF TESTING 1 When mounting and wiring are complete cover up the sensor to prevent it from detecting motion 2 Apply power to the sensor and light fixture Lights may tur...

Page 4: ...power to the sensor has been ON continuously for at least one minute then a Turn OFF power to the sensor The relay will close b Turn ON power to the sensor The load should come ON If not continue with step 2 2 Check power connections to the load 3 Check all sensor wire connections Verify the load wire is tightly secured Lights will not turn OFF 1 If there is no motion from people or equipment in t...

Reviews: