Wattstopper

 

®

High Bay • Line Voltage • Passive Infrared
IP65 Occupancy Sensors for Wet Locations

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24161 – 08/17  rev. 2

Catalog Number • Numéro de Catalogue • Número de Catálogo: HB300W  

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

DESCRIPTION AND OPERATION 

The HB300W low voltage occupancy sensor is designed for automatic lighting control in high bay wet location applications. The 

HB300W sensor contains a passive infrared sensor (PIR) and is modular being made up of two parts, a Sensor Module and a Lens. 

Time delay and PIR sensitivity values are set using DIP switches.

INSTALLATION OVERVIEW

1.  Review the ADJUSTMENTS section and complete any 

necessary DIP switch setting changes. 

2.  Mount the sensor so the lens is below the edge of the 

fixture and away from the lamps. Heat from the lamps 

could affect the sensor operation. 
Make sure that you have the appropriate accessories for the sensor 

mounting configuration. (See MOUNTING OPTIONS.)

3.  Assemble any necessary mounting accessories and attach them to the 

sensor module. Make sure that the flying leads from the sensor module 

cable are accessible inside the fixture. 

4.  Connect the line voltage and load wires to the power pack leads as 

shown in the applicable Wiring Diagram for the sensor module.
•  Do not allow bare wire to show. 
•  Make sure all connections are secure.
•  Check all gaskets for watertight fit.

5.  Connect the low voltage wires from the power pack to the sensor.
6.  Check sensor operation. Refer to the TESTING section.
7.  Attach the Lens to the HB300W as shown in the sensor assembly 

drawing. 

SPECIFICATIONS

Voltage ...........................................................................................24VDC
Wiring cable ................ 3 or 4-conductor 18AWG stranded, UL Style 2517
Unit Dimensions ...............................................4.08” diameter, 1.88” thick
Threaded nipple ................................................0.81” diameter, 0.40” long
 

fits standard 1/2” electrical conduit fitting

Weight ........................................................................ 0.28 lb (130 grams)
Material ......................................................... PC flame retardant material, 
 

 ............................................................UV resistant, indoor use only, 

 

 ............................................. minimum plastic wall thickness 2.5mm

Environment ......................................................................IP65 Compliant
Operating humidity .................................... 5 to 95% RH, non-condensing
Maximum Dew Point  ............................................................. 29°C (85°F)
US Patents: ........................................................5,640,113 and 5,804,991

CAUTION

TURN THE POWER OFF AT THE  

CIRCUIT BREAKER BEFORE INSTALLING THE SENSOR.

HB300W (sensor module)

HBLxW (lens module)

L7 lens may require pliers 

to remove the lens. (Grab 

one of the fins to remove.)

Tightening ring

Sensor Assembly

DIP switches

HB300W L3W

HB300W L7W