SPECIFICATIONS

Voltage ................................18-24VDC, 24VAC or Half-wave rectified AC
Current Consumption ...................................................................   35mA
Power Supply ...............................................  WattStopper Power Packs
Isolated Relay Rating ...................................................   1A @30VDC/VAC
Time Delay Adjustment .................................................   5 to 30 minutes
  Walk-Through Mode ................. 3 minutes if no activity after 30 sec.
  Test Mode ........................   5 sec. for 10 min. with DIP switch setting
PIR Adjustment..................................................  High or Low (DIP switch)
Ultrasonic Adjustment .................... Minimum to Maximum (trimpot), Off
 Frequency...................................................................................  40kHz
Light Level Adjustment ........................................................   8fc to 180+fc
Alerts.............................................................................Selectable Audible

US Patent:  6617560

DW-100-24

v3

Dual Technology Low Voltage

Wall Switch Occupancy Sensor 

Santa Clara, CA 95050

800.879.8585

Summary of Contents for WattStopper DW-100-24-LA

Page 1: ...o 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec for 10 min with DIP switch setting PIR Adjustment High or Low DIP switch Ultrasonic Adjustment Minimum to Maximum t...

Page 2: ...grammed for either Auto ON or Manual ON mode In either mode the load can be turned ON or OFF using the ON OFF button Manual ON DIP 8 ON With the ON Mode DIP switch in the ON position the occupant must...

Page 3: ...by approximately 50 Useful in cases where the PIR is detecting movement outside of the desired area also consider masking the lens and where heat sources cause unnecessary activation Low 50 DIP 4 ON...

Page 4: ...in order to deem the area occupied Both requires motion detection by the PIR and the Ultrasonic Either requires motion detection by only one technology PIR requires motion detection by the PIR Initia...

Page 5: ...d Relay Common must be used for proper operation Normally Open N O Closed when occupancy is detected The bottom terminal on the sensor is not used 4 Turn the power on 5 Test and adjust the sensor if n...

Page 6: ...9 is not used 5 6 Trigger Mode Initial Occupancy Maintain Occupancy Re trigger seconds duration Option C Both Both Both Standard Both Either 5 Either Option A Either Either 5 PIR Option B PIR PIR PIR...

Page 7: ...sounds Reset to Default Use the DIP Switch Settings tables on the previous page to return features to factory settings To reset the DW press and hold the ON OFF button for 10 seconds until a triple b...

Page 8: ...ource e g high wattage light bulb mounted near the sensor 3 Verify that the trimpot is not pointing at Service red LED ON If so rotate the trimpot to it s middle setting pointing up The Service settin...