Appendix I: Additional SRC Information
651
Assumption:
Upper Warning threshold is enabled.
Upper Warning = 20 (degrees Celsius)
Deassertion Hysteresis = 3 (degrees Celsius)
"Deassertion" level = 20-3 = 17 (degrees Celsius)
When the SRC detects that a temperature sensor's reading drops below
20 degrees Celsius, moving from the "above upper warning" range to the
"normal" range, either of the following may occur:
If the temperature falls between 20 and 17 degrees Celsius, the SRC
does NOT perform the "deassertion" action.
If the temperature drops to 17 degrees Celsius or lower, the SRC
performs the "deassertion" action to announce the end of the "above
upper warning" state.
Altitude Correction Factors
If a Raritan differential air pressure sensor is attached to your device,
the altitude you enter for the device can serve as an altitude correction
factor. That is, the reading of the differential air pressure sensor will be
multiplied by the correction factor to get a correct reading.
This table shows the relationship between different altitudes and
correction factors.
Altitude (meters)
Altitude (feet)
Correction factor
0 0 0.95
250 820 0.98
425 1394
1.00
500 1640
1.01
740 2428
1.04
1500 4921 1.15
2250 7382 1.26
3000 9842 1.38
Summary of Contents for Raritan SRC-0100
Page 114: ...Chapter 6 Using the Web Interface 102...
Page 291: ...Chapter 6 Using the Web Interface 279...
Page 301: ...Chapter 6 Using the Web Interface 289 6 Click Create to finish the creation...
Page 311: ...Chapter 6 Using the Web Interface 299...
Page 312: ...Chapter 6 Using the Web Interface 300 Continued...
Page 625: ...Appendix H RADIUS Configuration Illustration 613 Note If your SRC uses PAP then select PAP...
Page 630: ...Appendix H RADIUS Configuration Illustration 618 14 The new attribute is added Click OK...
Page 631: ...Appendix H RADIUS Configuration Illustration 619 15 Click Next to continue...