![LEGRAND Raritan PX3TS User Manual Download Page 595](http://html1.mh-extra.com/html/legrand/raritan-px3ts/raritan-px3ts_user-manual_1872008595.webp)
Chapter 9: Using the Command Line Interface
575
Specifying the Device Altitude
This command specifies the altitude of your PX3TS above sea level (in meters).
You must specify the altitude of PX3TS above sea level if a Raritan's differential
air pressure sensor is attached. This is because the device's altitude is
associated with the altitude correction factor. See
Altitude Correction Factors
(on page 844).
config:#
pdu deviceAltitude <altitude>
Variables:
•
<altitude> is an integer between -425 and 3000 meters.
•
Note that the lower limit "-425" is a negative value because some locations
are below the seal level.
Setting the Z Coordinate Format for Environmental Sensors
This command enables or disables the use of rack units for specifying the
height (Z coordinate) of environmental sensors.
config:#
pdu externalSensorsZCoordinateFormat <option>
Variables:
•
<option> is one of the options:
rackUnits
or
freeForm
.
Option
Description
rackUnits
The height of the Z coordinate is measured in
standard rack units.
When this is selected, you can type a numeric value in
the rack unit to describe the Z coordinate of any
environmental sensors or actuators.
freeForm
Any alphanumeric string can be used for specifying
the Z coordinate.
Note: After determining the format for the Z coordinate, you can set a value for
it. See
Setting the Z Coordinate
(on page 665).
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......