Appendix L: Additional PX3 Information
904
Threshold
Default value
Upper warning
65% of OCP rating
Hysteresis 1A
Total residual current:
Threshold
Default value
Upper critical
30mA
Hysteresis 15mA
Altitude Correction Factors
If a Raritan differential air pressure sensor is attached to your device,
the altitude you enter for the device can serve as an altitude correction
factor. That is, the reading of the differential air pressure sensor will be
multiplied by the correction factor to get a correct reading.
This table shows the relationship between different altitudes and
correction factors.
Altitude (meters)
Altitude (feet)
Correction factor
0 0 0.95
250 820 0.98
425 1394
1.00
500 1640
1.01
740 2428
1.04
1500 4921 1.15
2250 7382 1.26
3000 9842 1.38