Appendix G: PX3 Models with Residual Current Monitoring
813
RCM Residual Current and State Objects
The
inletSensorMeasurementsTable contains entries for RCM residual
current and states.
Use index
sensorType = 26 to retrieve the row for residual current.
Column
measurementsInletSensorValue contains the residual current.
Use index
sensorType = 27 to retrieve the row for RCM state. Column
measurementsInletSensorState contains the RCM state enumeration
value.
Setting RCM Thresholds
The inletSensorConfigurationTable contains a row for configuring RCM
thresholds. Use index
sensorType = 26 to reference the row. Columns
inletSensorUpperWarningThreshold, inletSensorUpperCriticalThreshold
and
inletSensorHysteresis set values for RCM warning, critical and
deassertion hysteresis respectively.
Running RCM Self-Test
To initiate RCM self-test using SNMP, set column
rcmState to value 29 in
table
rcmSelfTestTable.
For Type B "M18" models, the self-test feature will perform tests on all
poles of the selected inlet simultaneously.
CLI Operations for RCM
For information on entering and using the CLI, see
Using the Command
Line Interface
(on page 511).
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...