Appendix G: PX3 Models with Residual Current Monitoring
805
Setting RCM Current Thresholds
The RCM current thresholds define the critical, warning and normal
range of residual current.
For Type A, RCM current thresholds are the thresholds of residual
AC current.
For Type B, they are the thresholds of total residual current
including AC and DC current.
Tip: To configure the thresholds of residual DC current, if the RCM DC
sensor is available on your PDU, see
Setting RCM DC Current
Thresholds
(on page 806).
To configure RCM current thresholds and run self-test:
1.
Click Inlet to open the Inlet page.
2.
In the Residual Current Monitor section, click Setup.
3.
Set up RCM thresholds.
a.
Enable or disable the RCM critical threshold. Residual current
greater than this value triggers Critical RCM state.
b.
Enable or disable the RCM warning threshold. Residual current
greater than this value triggers Warning RCM state.
c.
Determine the residual current decrease to end Warning or
Critical RCM state.
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...