124 Legrand PDU User Guide
Example
Physical position
Port 1
Connected to the sensor port #1.
Port 1,
Channel 2
Connected to the sensor port #1.
The sensor/actuator is the 2nd channel of the sensor package.
Port 1,
Chain Position 4
Connected to the sensor port #1.
The sensor/actuator is located in the 4th sensor package of the sensor chain.
Port 1,
Chain Position 3,
Channel 2
Connected to the sensor port #1.
The sensor/actuator is located in the 3rd sensor package of the sensor chain.
It is the 2nd channel of the sensor package.
Port 1,
Chain Position 1,
Hub Port 2,
Chain Position 3
Connected to the sensor port #1.
Connected to the 2nd port of the DPX3-ENVHUB4 sensor hub, which shows
the following two pieces of information:
The hub's position in the sensor chain -- "Chain Position 1"
The hub port where this particular sensor package is connected -- "Hub
Port 2"
The sensor/actuator is located in the 3rd sensor package of the sensor chain
connected to the hub's port 2.
Managing One Sensor or Actuator
If you are managing only one sensor or actuator, you can assign the desired ID number to it. Note that you
cannot assign ID numbers when managing multiple sensors/actuators at a time.
Tip: When the total of managed sensors/actuators reaches the maximum value (32), you cannot manage
additional ones. The only way to manage any sensor/actuator is to release or replace the managed ones. To
replace a managed one, assign an ID number to it by following the procedure below. To release any one,
see
Peripherals
(on page 116).
To manage only one sensor/actuator:
1. From the list of "unmanaged" sensors/actuators, click the one you want to manage.
2. The "Manage peripheral device" dialog appears.