PRO1 Sentry Switched DC PDU
171 of 211
set location
Sets the system location string.
Command Syntax
set location <location string>
Parameters
The
set location
command uses the following parameter:
location string
Location string text for system location. 0-63 characters.
Command Access
Admin level only
set outlet
Sets outlet configuration values.
Command Syntax
set outlet branchevent [disabled | enabled] <name | id | ALL>
set outlet chglogging [disabled | enabled]
set outlet email [disabled | enabled] <name | id | ALL>
set outlet load [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set outlet load hyst <value>
set outlet name <name | id> <new name>
set outlet snmpt [disabled | enabled] <name | id | ALL>
set outlet watts [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set outlet watts hyst <value>
Parameters
The
set outlet
command uses the following parameters:
chglogging
Sets logging for system outlet state changes
Sets email notifications for outlet events.
extondelay
Sets an extra on delay when turning on an outlet. 0-900 seconds.
host
Sets the hostname for an outlet for script or shutdown actions.
0-63 characters.
hyst
Sets the hysteresis between event state and recovery.
load
Sets the current load for an outlet. min 0.0A, max (max current) in
show
outlets
command, hyst 1.0-10.0A (default 1.0A)
lock
Sets if control actions are disabled for an outlet after wakeup state is applied.
pf
Sets the power factor. min 0.00, max 1.00, hyst 0.0-0.20 (default 0.02)
rebootdelay
Sets an extra on delay when rebooting an outlet (5-600 seconds).
script
Sets to additionally send request to have shutdown agent run a script before
shutting down the host.
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...