1
LE05156AE
Int configuration software
0 626 00
Important:
According to the European directive 91/157/EEC dated 18 March 1991, the batteries in this interface, which contain cadmium, may be dangerous for
the environment.
Technical characteristics:
• Power supply
: 230V~50Hz
• Power consumption
: 5 W 45 mA
• Battery
: 9 V/110 mAh NiCd/NiMH
• Fuse protection
: BUS 0.5 A F 250 V~(5 x 20)
• Connection
: Mains, 2 terminals 1 x 1.5 mm²
• Cable sizes
: - Remote controls, 2 terminals 1 x 1.5 mm²
- RS 232, 5 terminals 1 x 1.5 mm²
- RS 485, 2 terminals 1 x 1.5 mm²
- Fault relays, 6 terminals 1 x 1.5 mm²
- RJ 45 for connection to IP network
- Mini USB for direct connection to PC (max 1.5 m)
• Case insulation
: Class II
• Operating temperature : + 5 °C to + 40 °C
• Storage temperature
: - 10 °C to + 60 °C
• Dimensions
: W 178.2 mm x H 87.1 mm
10
modules
To use this interface, you must first configure it with the configuration programme delivered on the USB-stick and using guide LE05022XX.
1
Fault relay 1 connection terminals
2
Fault relay 2 connection terminals
3
Fault relay indicator
4
USB socket
5
Mains supply terminals
6
Connection terminals for RS485 (2 conductors)
Connection terminals for RS232 (5 conductors)
Battery charge indicator
9
Connection terminals for exterior control box catalogue no.: 0 039 00
BUS connection terminals
BUS presence indicator
Emergency lighting unit on/off buttons
Unit MAC address
RJ 45 connector for IP network
IP network presence indicator
Unit address selector
BUS protection fuse
Reset button
Description
Network
Reset
626 00
1
2
BUS
RS 485
1
2
3