LEGRAND 0 489 35 Technical Data Manual Download Page 1

Cat. No(s): 0 489 35

Technical data sheet: S000088482EN-1 

Updated:  

Created: 02/01/2017

1/8

PIR+US ceiling mount sensors

(DALI)

CONTENTS

 Page

1. 

Use  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2

Technical characteristics  . . . . . . . . . . . . . . . . .1

3. 

Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

4. 

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

5. 

 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

6. 

 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

7. 

Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

8. 

Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

9. 

Care  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

10. 

Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

11. 

Troubleshooting  . . . . . . . . . . . . . . . . . . . . . . . .8 

1. USE

2. TECHNICAL CHARACTERISTICS

DALI sensor Cat. No. 0 489 35 is a device which measures the daylight 

level and detects presence of people using dual technology (passive 

infrared and ultrasonic (PIR + US)).
It can be surface-mounted on a concrete ceiling using box 

 

Cat. No. 0 488 75, or flush-mounted directly in a suspended ceiling using 

claws or in a flush-mounting box Cat. No. 0 800 31.
It is suitable for indoor workspaces such as offices, meeting rooms, 

classrooms, etc and it can be used on its own or in combination with 

DALI power supply/wiring unit Cat No. 0 488 76.
This sensor can manage up to 2 groups of dimmer ECGs, “window” 

and “corridor” type (containing a maximum of 64 ECGs), for which it is 

possible to configure an offset light level.
If it is used in combination with DALI power supply/wiring unit  

Cat No. 0 488 76, it can manage up to three ECG groups (64 ECGs max).
These groups are made up as follows: 2 “window” and “corridor” groups 

which can be used to dim the lighting, for which it is possible to set a 

light level offset, and a “display board” group which can only be switched 

ON/OFF.
This sensor is fully configured using configuration tool Cat. No. 0 882 30/ 

BMSO4001 with which it is possible to: 

- Distribute DALI ECG addresses 

- Pair DALI ECGs with their sensor and their group (window, corridor or 

display board) 

- Define the light level offset between the “window” group and the 

“corridor” group 

- Designate Master and Slave sensors 

- Define the standby level when there is no detection  

- Define the standby time  

- Configure all the other sensor settings (for example, daylight setpoint, 

time the lighting remains on after detection, choice of detection 

technology, operating mode, etc.)
DALI sensor Cat. No. 0 489 35 is powered with 16 VDC by the DALI bus.
A DALI power supply Cat No. 0 035 15 or 0 035 13 can supply this 

voltage to the DALI BUS with a maximum of 200 mA, and the DALI unit  

Cat No. 0 488 76 also acts as the bus power supply.

Voltage: 12-20 V

=

  

Consumption: 25 mA 

Wiring: 

- Power:   2 x 2.5 mm

2

 

 

DALI < 1.5 mm

2

Usage temperature: -5°C to +45°C

Storage temperature: -20°C to +70°C

Impact resistance: IK04

Penetration by solid and liquid matter: IP20

Weight: 115 g

DALI configuration red 

LED

US sensor

PIR sensor

TEST button

Detection LED

IR transmission/ 

reception cell

Light level cell

Summary of Contents for 0 489 35

Page 1: ...roups are made up as follows 2 window and corridor groups which can be used to dim the lighting for which it is possible to set a light level offset and a display board group which can only be switche...

Page 2: ...t No s 0 489 35 PIR US ceiling mount sensors DALI CONTENTS 3 1 Sensor location 3 2 Recommended light exposure 3 INSTALLATION US PIR 2 5 m 1 5 m 3 3 Mounting 3 4 Recommended light exposure 3 5 Removal...

Page 3: ...ensors DALI CONTENTS 4 DIMENSIONS 50 58 50 1 2 2 5 1 Wiring with a single sensor 5 CONNECTION D 5 2 Wiring with several sensors 5 CONNECTION CONTINUED D x 64 max 0 488 72 Cat Nos 0 035 13 15 200 mA ma...

Page 4: ...be connected to a master sensor via Cat No 048878 150m max D D 100 m 0 5 mm2 150 m 0 75 mm2 300 m 1 5 mm2 25 mA 2 mA 5 4 Wiring with several sensors one control unit and a DALI unit Cat No 0 488 76 D...

Page 5: ...ch off if another movement is detected within a 30 second period the lighting switches on automatically The Restart function must be enabled After 30 seconds the lighting has to be switched on manuall...

Page 6: ...ly possible if the installation includes a DALI unit Cat No 0 488 76 The lighting is only switched on when presence is detected and can be switched off with a push button Master Slave parameter settin...

Page 7: ...5 6 25 3 5 5 25 6 5 35 4 6 5 35 7 5 45 5 6 30 10 5 90 6 4 15 5 5 25 High sensitivity 75 Very high sensitivity 100 m surface m2 m surface m2 Height m 2 5 6 5 30 8 50 3 8 5 60 11 5 100 4 12 5 125 14 155...

Page 8: ...h light provided Enable the regulation function Reduce the daylight setpoint Decrease the power of the luminaires Time delay too short Detection sensitivity too low Daylight setpoint too low Increase...

Reviews: