![LEGRAND 0 489 35 Technical Data Manual Download Page 1](http://html1.mh-extra.com/html/legrand/0-489-35/0-489-35_technical-data-manual_1870346001.webp)
Cat. No(s): 0 489 35
Technical data sheet: S000088482EN-1
Updated:
Created: 02/01/2017
1/8
PIR+US ceiling mount sensors
(DALI)
CONTENTS
Page
Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Technical characteristics . . . . . . . . . . . . . . . . .1
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .8
1. USE
2. TECHNICAL CHARACTERISTICS
DALI sensor Cat. No. 0 489 35 is a device which measures the daylight
level and detects presence of people using dual technology (passive
infrared and ultrasonic (PIR + US)).
It can be surface-mounted on a concrete ceiling using box
Cat. No. 0 488 75, or flush-mounted directly in a suspended ceiling using
claws or in a flush-mounting box Cat. No. 0 800 31.
It is suitable for indoor workspaces such as offices, meeting rooms,
classrooms, etc and it can be used on its own or in combination with
DALI power supply/wiring unit Cat No. 0 488 76.
This sensor can manage up to 2 groups of dimmer ECGs, “window”
and “corridor” type (containing a maximum of 64 ECGs), for which it is
possible to configure an offset light level.
If it is used in combination with DALI power supply/wiring unit
Cat No. 0 488 76, it can manage up to three ECG groups (64 ECGs max).
These groups are made up as follows: 2 “window” and “corridor” groups
which can be used to dim the lighting, for which it is possible to set a
light level offset, and a “display board” group which can only be switched
ON/OFF.
This sensor is fully configured using configuration tool Cat. No. 0 882 30/
BMSO4001 with which it is possible to:
- Distribute DALI ECG addresses
- Pair DALI ECGs with their sensor and their group (window, corridor or
display board)
- Define the light level offset between the “window” group and the
“corridor” group
- Designate Master and Slave sensors
- Define the standby level when there is no detection
- Define the standby time
- Configure all the other sensor settings (for example, daylight setpoint,
time the lighting remains on after detection, choice of detection
technology, operating mode, etc.)
DALI sensor Cat. No. 0 489 35 is powered with 16 VDC by the DALI bus.
A DALI power supply Cat No. 0 035 15 or 0 035 13 can supply this
voltage to the DALI BUS with a maximum of 200 mA, and the DALI unit
Cat No. 0 488 76 also acts as the bus power supply.
Voltage: 12-20 V
=
Consumption: 25 mA
Wiring:
- Power: 2 x 2.5 mm
2
DALI < 1.5 mm
2
Usage temperature: -5°C to +45°C
Storage temperature: -20°C to +70°C
Impact resistance: IK04
Penetration by solid and liquid matter: IP20
Weight: 115 g
DALI configuration red
LED
US sensor
PIR sensor
TEST button
Detection LED
IR transmission/
reception cell
Light level cell