background image

6/8

CoNTeNTs

Technical data sheet: S000077897EN-1 

Updated:  

Created: 10/03/2014

Cat. No(s): 0 489 14

Lighting management sensor - PIR

  8. seTTINgs

8.1   Detection parameters

  Time delay:

 Length of time the load is on after detection occurs. 

 sensitivity:

 Detection range setting.

modes:

 auto on/auto off mode:

Comes on automatically: 

- At the detection of a presence if there is an insufficient natural level of 

light. 

Turns off automatically: 

- If no presence is detected and at the end of the time delay set. 

- Or if the natural light level is sufficient (regulation activated).

Any new detection triggers an automatic switch-on if there is 

insufficient light.

 Walk-through mode:

-  If no presence is detected in the 20 seconds following an initial 

detection, the product will cut off the load after 3 minutes.

-  If another presence is detected in the 3 minutes following initial 

detection, the device will cut off the load at the end of the set time 

delay.

 manual on/auto off mode:

Manual switch-on, automatic switch-off: 

-  When no presence is detected and at the end of the set time delay.
After switch-off, any new detection within a 30-second period triggers 

an automatic switch-on. The Restart function must be activated.

After 30 seconds the device is switched on via a manual control.

Detection system:
Initial detection:

 The load is switched on as soon as the first detection 

occurs if the natural light level is below the light level threshold.

maintain: 

The load remains active if another presence is detected.

Restart:

 In manual mode. After switch-off, any new detection within a 

30-second period triggers an automatic switch-on.

After 30 seconds the device must be switched on manually. 

Possible in Manual on/Auto off mode only.

alarm:

 an audible signal is emitted before switch-off (1 minute before, 

then 30 seconds, then 10 seconds).

sensor parameter

Default 

value

modifiable 

parameters

Configuration 

tools

0 882 30 0 882 35

Time delay

15 min

3, 5, 10, 15, 20 min

0 - 59 min 59 s

sensitivity

PIR (very 

high)

Low, medium, 

high, very high

m

odes

auto on/auto off

Inactive

Activate/

Deactivate

Walk-through 

mode

Active

Activate/

Deactivate

manual on/auto 

off

Inactive

Activate/

Deactivate

Detection  system

Initial

PIR

Not modifiable

maintain

PIR

Not modifiable

Restart

PIR

PIR and/or US, PIR, 

US, Deactivate

alarm

Inactive

Activate/

Deactivate

   8.  seTTINgs (continued)

8.2   Light parameters

  Light level threshold:

 Value at which the load comes on if the 

natural light level is less than the setting.

  eye function:

 Value 0 (eye on configuration tool 0 882 30) is 

used to save the ambient light level in the room as a light level 

threshold.

advanced mode:

   Calibration:

 The ambient light level measured with a luxmeter 

must then be transmitted to the sensor.

   Regulation:

 Automatic switch-off of the load 10 minutes after the 

light level threshold is exceeded with an additional safety threshold 

(to avoid lights switching off at the wrong moment).

Light contribution:

 Quantity of additional lux brought in by the load 

being switched on.  

When the light contribution parameter is set to "Auto" (value 0) on the 

configuration tool Cat. No. 0 882 30, the sensor automatically calculates 

the light contribution.

  8.3  modifying the parameters using the configuration tools

attention: 

Do not put on the blanking plate when  

modifying parameters via a configuration tool.

• 0 882 35: Simplified configuration tool

 

• 0 882 30: Advanced configuration tool

When the sensor receives an IR command via a configuration tool,  

it emits a beep acknowledging the modification.

For more information about setting parameters, refer to the data sheet 

for the configuration tool Cat. No. 0 882 30.

-  Restore to factory settings:

1

st

 press: Short press on LEARN, the LED flashes slowly.

2

nd

 press:  Hold down LEARN for 10 seconds until the LED flashes 

quickly.

sensor parameter

Default 

value

modifiable 

parameters

Configuration 

tools

0 882 30 0 882 35

Light level threshold

300 lux

20, 100, 300, 500, 

1000 lux

5 - 1275 lux

a

dvanced

 

mode

Calibration

0 - 99,995 lux

Regulation

Active

Activate/

Deactivate

Light contribu-

tion

Auto

Auto - 1275 lux

Summary of Contents for 0 489 14

Page 1: ...00 operations Mains zero breaking in order to limit the effect of induced currents on cut off relays by fluorescent loads in particular this sensor breaks the voltage at mains zero Switching occurs wh...

Page 2: ...gement sensor PIR 3 Dimensions With protective cover 84 46 31 118 2 1 A max SN S2 S1 100 m max 8 5 A max PB L 8 5 A max 2 1 A max PB 100 m max 8 5 A max 2 1 A max V U 30 V 4 Connection 4 1 Wiring with...

Page 3: ...0 489 14 Lighting management sensor PIR PIR 2 5 m 3 5 m 1 2 2 1 A max SN S2 S1 100 m max 8 5 A max 8 5 A max 8 5 A max PB LN L2 L1 4 Connection continued 4 4 Wiring for several loads connected in par...

Page 4: ...Updated Created 10 03 2014 Cat No s 0 489 14 Lighting management sensor PIR 6 INSTALLATION continued 6 3 Fitting 6 INSTALLATION continued 6 3 Fitting continued 3 50 67 4 0 489 71 6 4 Choice of detect...

Page 5: ...he sensors S switch to the ON state one short press all the sensors S inversion of OFF to ON or ON to OFF L1 OFF L2 OFF Ln OFF S1 OFF S2 OFF Sn OFF 1 s L1 ON L2 ON Ln ON S1 ON S2 ON Sn ON L1 ON L2 ON...

Page 6: ...5 10 15 20 min 0 59 min 59 s Sensitivity PIR very high Low medium high very high Modes Auto on Auto off Inactive Activate Deactivate Walk through mode Active Activate Deactivate Manual on Auto off In...

Page 7: ...0 4 m Height 2 5 m Sensitivity Low 25 Sensitivity Medium 50 Sensitivity High 75 Sensitivity Very high 100 a m b m a m b m a m b m a m b m 2 6 3 6 4 6 4 6 b a CK 12 m PIR 2 5 m 0 4 Height 2 5 m Sensit...

Page 8: ...ents vibrations and radiators can cause unintended operation 1 Reduce the sensitivity level 2 If the interference continues using the configuration tool go into the Detection system parameters select...

Reviews: