LEGRAND 0 488 34 Manual Download Page 1

1/7

Technical data sheet: S000088605EN-1  

Updated on:  

Created: 03/04/2015

Catalogue number(s): 0 488 34

SCS motion sensors  

Surface/wall mounting - PIR

  1. USe

This is a passive infrared (PIR) device adapted to detecting presence and 

measuring the level of natural light. 

It can be installed directly on a wall, flush-mounted in a wiring accessory 

box and installed in internal or external corners with fixing accessory 

Cat. No. 0 489 71.

It is suitable for indoor or outdoor passageways such as atriums, 

corridors, car parks, cellars, etc.

Main possible functions:

-  Switching/Dimming: in automatic mode, or manual mode in 

association with a control unit

-  Configuring the operating mode: Auto ON/OFF, Manual ON/Auto OFF, 

Walk-through

- Defining a light level threshold to be maintained

- Triggering scenarios according to presence/absence

The mode and settings are configured using configurators, with 

MHSuite and mobile configurators Cat. Nos. 0 882 30 or 0 882 35.

  2. TeChnICal ChaRaCTeRISTICS

Voltage: 27 V

=

No-load power consumption: 20 mA max.

Connection between the sensor and controller: BUS/SCS cable

Flush-mounting diameter:  65 mm without a flush-mounting box, 

68 mm with a flush-mounting box

Weight: 180 g

Impact resistance: IK04

Penetration by solid and liquid matter: IP55

Operating temperature: -5°C to +45°C

Storage temperature: -20°C to +70°C

Cover removed

ConTenTS 

Page

1. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2. Technical characteristics  . . . . . . . . . . . . . . . .1

3. Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

4. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

5. Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

6. Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

7. Settings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

8. Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . .5

9. Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . .6

10. Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

11. Standards and certifications. . . . . . . . . . . . .7

12. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .7

IP55

PIR sensor

Light  

level cell

LEARN LED

IR transmission/

reception LED

Detection LED

LEARN button

  3. DImenSIonS

With protective cover

84

46.5

31

115.5

  4. ConneCTIon

BUS/SCS

Summary of Contents for 0 488 34

Page 1: ...riggering scenarios according to presence absence The mode and settings are configured using configurators with MHSuite and mobile configurators Cat Nos 088230 or 088235 2 Technical characteristics Voltage 27 V No load power consumption 20 mA max Connection between the sensor and controller BUS SCS cable Flush mounting diameter 65 mm without a flush mounting box 68 mm with a flush mounting box Wei...

Page 2: ...n Created 03 04 2015 Catalogue number s 0 488 34 SCS motion sensors Surface wall mounting PIR 6 Installation 6 1 Sensor positioning 5 Removal 1 2 PIR 2 5 m 3 5 m 6 2 Recommended light exposure 6 INSTALLATION continued 6 3 Positioning 3 50 Ø 67 2 60 mm 1 60 mm ...

Page 3: ... Configuration tools 0 882 30 0 882 35 Time delay 15 min 3 5 10 15 20 min 30sec 255hrs 59min 59s Sensitivity PIR very high Low medium high very high Modes Auto ON Auto OFF Inactive Activated Deactivated Walk through mode Active Activated Deactivated Manual ON Auto OFF Inactive Activated Deactivated Partial ON Group OFF Inactive Activated Deactivated Detection system Initial PIR Non modifiable Main...

Page 4: ...s continued 7 1 Detection parameters continued Modes Auto ON Auto OFF mode The lighting switches on automatically When presence is detected and there is insufficient natural light The lighting switches off automatically If no presence is detected at the end of the set time delay Or if there is an adequate level of natural light regulation function activated Any new detection triggers an automatic ...

Page 5: ...ange with presence detection 1 Automatic ON OFF mode light level mea sure without presence detection 2 Supervision mode 3 Automatic ON OFF mode setting range with detection 4 Automatic ON OFF mode setting range without detection The S configurator sensor sensitivity The sensor s sensitivity can be set using the S configurator If the sensor is a Dual Tech then the sensitivity selected is applied to...

Page 6: ... m 2 4 3 6 4 6 5 6 Maximum installation height 3 m Height 2 5 m Low Sensitivity 25 Medium Sensitivity 50 High Sensitivity 75 Very high Sensitivity 100 a m b m a m b m a m b m a m b m 8 4 10 6 12 6 15 6 Maximum installation height 3 m 9 Performance 9 1 Radial movement 9 Performance continued 9 2 Tangential movement 9 3 Performance with blanking plate CLICK SNAP b b a a CLICK SNAP CLICK SNAP 15 m 15...

Page 7: ...not switch off during the day when there is an adequate natural light level Regulation function not active Light level threshold set too high Light contribution is too high Activate the regulation function Reduce the light level threshold Check that the sensor is positioned correctly in relation to the window Decrease the power of the luminaires The lighting switches off when there are people pres...