Technical data sheet: S000114123EN-1 

Updated: 

Created: 18/01/2021

Cat. No(s): 0 026 72/73/74/76/78/79

KNX controller multi-application DIN

   7 .  COMMUNICATION OBJECTS (continued)

7 .7 "Switch" parameter (continued)
7 .7 .2 "A1 - Function" parameter (continued)
7 .7 .2 .1 A1 - Function" parameter (continued)

Duration of staircase lighting [min]/ [sec]

0…

*5

…240[min]

*0

…59        [sec]

Staircase function on time is calculated by “

duration of staircase 

lighting”

. Staircase lighting time is defined by this parameter. At 

the end of the on time, the relay off or active the staircase warning 

functions.

Staircase retrigger

*not retriggerable

  yes retriggerable

  up to staircase lighting time 2x

  up to staircase lighting time 3x

  up to staircase lighting time 4x

  up to staircase lighting time 5x

This parameter defines whether the staircase on time can be retrigger 

able or not so the on time can be extended by ‘Enable staircase 

function’. You can repeat retrigger function until the repeater count 

reached the maximum value (2x, 3x, 4x, 5x). If the parameter selects 

"

not retriggerable

", staircase on time doesn’t extend.

Reaction to OFF telegram

*switch off

  

ignore

After this parameter selected "

switching off

", "

ignored

". Enable 

staircase function’ communication object ‘disable’ command. 

Staircase time can be changed by object

  

yes

*no

"

Staircase lighting duration

" communication object is visible if a 

"

Staircase time can be changed by object

" parameter selects "

yes

This communication object is 2 byte. The value defines the staircase 

on time in second. 
NOTE: After a bus voltage fails, staircase on time returns default value 

(Duration of staircase lighting).

Restart staircase after “Permanent ON”

  

yes

*no

If this parameter is selected "

yes

", receive "

Permanent ON

communication object after restart staircase function.

Activate pre-warning time?

  

yes

*no

The warning function can be activated by this parameter select "

yes

". 

Then, you can adjust pre-warning time, number of pre-warning and 

time for pre-warning interval. The warning function is for warning 

that the staircase lighting time run out and the lights are switched 

off soon. In the warning, lights short turn off. Switch status is ON until 

finish warning time.

Pre-warning time Minutes (0…59)

Second (0…59)

*0…59

  0…

*30

…59

How long the lights shall be switched on in the period.

Number of pre-warning (1…10)

1…

*2

…10

Enter the number of how many blink doing in the warning.

Time for pre-warning intervals 

Seconds (0…59)

0…

*3

…59

How long the lights shall be switched off in the period.

Activate on delay

  

yes

*no

This parameter is used delay to switch off position before staircase 

start.

   7 .  COMMUNICATION OBJECTS (continued)

7 .7 "Switch" parameter (continued)
7 .7 .2 "A1 - Function" parameter (continued)
7 .7 .2 .2 " A1 - External logic" parameter

Logic function can be used independently for each output. With this 

function, the ‘Switch’ object can be logically linked with the "

External 

logic input

". Channel relay switch a result of the logic operation. For 

example, "

Switch

" object value 1 and "

External logic input

" object 

value 0 relay switch as a result of 1 & 0 operation.

External logic function type

  *AND

 

   OR

    XOR

This parameter selects the type of logic function between "

Switch

and "

External logic input

" objects.

Invert result

  

yes

*no

If you want to inverted logic function result, you should select "

yes

".

Logic object value after bus voltage return  

  “1”

*”0”

This parameter defines the value of the "

External logic input

" object 

after bus voltage return.

Note:  

The values of the "

External logic

" communication objects doesn’t 

store at the bus voltage failure.

7 .7 .2 .3 "A1 - Sweep" parameter

Sweep function only starts to operate if the relay is switched ON. It’s an 

alternative way for turning off the relay with pre-warning. The sweep 

function is desired to warn a person that lights will go out shortly.

Send counter value

1…

*3

…10

The lamps connected to the relay will be switched off as many times. 

Enter the number of how many blink doing in the warning.

Blink on time

0,5sec…

*1sec

…5sec

How long the lights shall be switched on in the period.

CONTENTS

Summary of Contents for 0 026 72

Page 1: ...ch Sensor parameter 10 7 5 2 a Switch Dim Sensor parameter 11 7 5 2 a Switch Dim Sensor parameter continued 11 7 5 3 a Blind Sensor parameter 11 7 5 4 a Value Forced Operation parameter 12 7 6 Enable...

Page 2: ...n parameter 23 7 10 2 A B1 Status Message parameter 24 7 10 3 A B1 Automatic Operation parameter 25 7 10 4 A B1 Direct Mode parameter 25 7 11 Function Chart 26 7 12 Object Description 26 7 12 1 Genera...

Page 3: ...ut x4 AC Blind x2 DC Blind x1 2 Point valve x2 3 point valve x2 Suitable for switching resistive capacitive and inductive loads as well as fluorescent lamp loads according to EN 60 669 A single switch...

Page 4: ...4123EN 1 Updated Created 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION 0 026 72 73 AC Motor D2 NA Fan1 Fan2 Fan3 4 CONNECTION continued 0 026 74 AC Moto...

Page 5: ...ted 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION continued 0 026 76 AC Motor AC Motor DC Motor F G DC Motor F G 4 CONNECTION continued 0 026 78 79 AC M...

Page 6: ...S4 or higher Important A detailed information about parameter configuration can be found in Product Manual of device Installation and commissioning of device may only be implemented by trained electri...

Page 7: ...100 1 bit CW 98 Output A1 Staircase lighting duration 7 007 2 byte CRW Output A Output A B Move to position height 0 255 5 001 1 byte CW Fan A B1 Switch speed 3 1 001 1 bit CW Control input Fault con...

Page 8: ...e sent freely within a period Note If the value of the object cannot be sent in the time of a period The object is buffered for the next period time The buffered object will be updated if the object v...

Page 9: ...valuate the transmitted scene address and switches the output to the stored scene value A scene is activated when it receives its scene number at the scene object The storing of the current channel va...

Page 10: ...is distinction between short and long operation The contact type of the push button attached to the channel is adjusted here Cyclic transmission of object no switch OFF switch ON always This paramete...

Page 11: ...operation STOP telegram sends at the end of operation Brightness change on every sent telegram 100 6 25 1 56 This parameter is only visible with the Dimming steps options This parameter is cyclically...

Page 12: ...op command is sent such as STOP Lamella adj UP or STOP Lamella adj DOWN 1 Shutter MOVE UP STOP Lamella UP 2 Shutter MOVE DOWN STOP Lamella DOWN 2 button stepping On operation Stop lamella adjustment T...

Page 13: ...n shutter blind DC fan coil valve control individually Both output group can be combined into one DC blind In DC blind operation the four relay contacts of the device can be used to control electrical...

Page 14: ...bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the output The relay can be open close...

Page 15: ...mber of pre warning and time for pre warning interval The warning function is for warning that the staircase lighting time run out and the lights are switched off soon In the warning lights short turn...

Page 16: ...B General parameter continued Behavior after ETS programming or after ETS reset Behavior bus voltage failure no reaction up down stop position 1 2 3 4 approach position This parameter can be used to c...

Page 17: ...e Trigger reference movement communication object is visible The reference movement is triggered via this communication object In long time slight inaccuracies can occur so the upper and lower end pos...

Page 18: ...This function allows you set a height position or slat position directly using with communication object Enable communication objects Move to pos Height Move slat 0 255 no yes The communication Move t...

Page 19: ...havior in case of rain alarm Behavior in case of frost alarm no reaction up down stop position 1 position 2 position 3 position 4 individual position When the alarm is activated the blind moves this p...

Page 20: ...tion communication object is updated After the bus voltage return forced position function set to the parametrized position Set the parameter to no forced position active The forced operation is deact...

Page 21: ...ING is deactivated Set the parameter to 1 When the telegram is received 1 HEATING operation is activated COOLING is deactivated Monitoring control valves yes no This parameter activate the thermostat...

Page 22: ...vel time This time is maximum one minute Valve limitation yes no The limitation of the control value limits the height of the control value The limitation is activated when a value is chosen which is...

Page 23: ...ons Thus initially the number of fan levels required for the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels...

Page 24: ...ime has elapsed 7 COMMUNICATION OBJECTS continued 7 10 Fan Coil parameter continued 7 10 2 A B1 Status Message parameter Enable communication object Status fan speed x 1 bit yes no The data format for...

Page 25: ...peed In s 0 65535 0 65535 This parameter defines the dwell time for a fan speed of the fan until it switches to the next higher or lower fan speed 0 no delay time for switching 7 COMMUNICATION OBJECTS...

Page 26: ...x Des 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x...

Page 27: ...d operation 1 byte 0 255 DPT 5 001 brightness value 2 byte 32768 32767 DPT 7 001 signed value 2 byte 0 65535 DPT 8 001 unsigned value 4 byte float value DPT14 068 temperature 4 byte 0 4294967295 DPT12...

Page 28: ...or 4 104 Trigger reference movement Output A DTP 1 008 1 bit CW This object is triggered the reference movement If the telegram is received the blind is moved up or down end position Then the blind c...

Page 29: ...OMMUNICATION OBJECTS continued 7 17 Fan Object Description No Object name Name DTP Type Length Flags 95 Fan speed switch Fan DPT 5 010 1 byte CW This object is used to switch on fan speed via 1 byte o...

Reviews: