1
TECHNICAL SPECIFICATIONS
Model
LI2200
Capacity (VA)
2200VA
Capacity (Watts)
1500W
Input
Voltage Range
85 -150Vac
Frequency Range
47 - 63Hz
Output
On Battery Output Voltage
Pure Sine Wave at /- 5%
On Battery Output Frequency
60Hz +/- 1%
Transfer Time (Typical)
4ms
Overload Protection
On Utility: Circuit Breaker,
On Battery: Internal Current Limiting
Surge Protection and Filtering
Lightning / Surge Protection
Yes
Internet Ready (DSL / Phone /
FAX / Modem Protection)
RJ11/RJ45(One In/One Out)
Physical
Total # of UPS Receptacles
6
Maximum Dimensions(cm)
2U Rack, 43.3x8.8x38.8
Weight (Kg)
32.1
Battery
Sealed Maintenance Free Lead
Acid Battery
12Vdc 9AHx4
Typical Recharge Time
8 Hours
Warning Diagnostics
Indicators
Power On, Using Battery, AVR, Wiring Fault,
Load Level, Battery Level
Audible Alarms
On Battery, Low Battery, Overload
Environmental
Operating Temperature
+ 32°F to 95°F (0°C to 35°C)
Operating Relative Humidity
0 to 95% NON-CONDENSING
Communication
SeeUPS2020 Software
Windows 95/98/ME/NT/2000/XP compatible
Management
Self-Test
Manual Self-Test
Auto-Charger
Yes
Auto-Restart
Yes
USB
Yes
10