background image

 

Operating Mode Display: 

 

Snowflake “ON” – compressor enabled in 
run cycle; control displays current cabinet 
temperature. 

 

Snowflake “Flashing” – anti short cycle 
delay enabled to protect the compressor 
from trying to start too frequently. 

 

Melting Snowflake “ON” – defrost in 
progress, control displays the letters “dE”

 

 

Melting Snowflake “Flashing” – defrost 
delayed by output activation setting. 

 

 

Fan “ON” - Certain models that utilize the 
XRO6 controller have the capability to 
operate the evaporator fans on and off 
independently from the defrost circuit. 

 

 

To view the control’s programmed “Set 
Point” (cut-out temperature): press and 
release the “Set Key.” 

 

To initiate a manual defrost cycle: press 
and hold the “Manual Defrost Key” for 
more than 3 seconds. 

Note:

 Manual Defrost will not initiate unless the 

unit is at standard operating temperatures and the 
evaporator probe is under the defrost termination 
setting.  

Electronic Control Operation: 

The electronic control combines the functions of 
both the mechanical thermostat and defrost timer 
into a single control. The control also offers the 
consumer the capability of monitoring the 
operational status of the merchandiser via the icon 
and digital temperature display (located on the 
face of the control). The controller has been 
programmed by Leer to operate the merchandiser 
within the design parameters of the refrigeration 
system. The set-point (cut-out) for these controls 
has programmed parameters for 14-16°F, with a 
differential of 6-8°F Should the user desire to alter 
the Set-Point, the new set-points should not 
/- 4° of the original factory setting. Do 
not alter any of the programming parameters in 
the controls without first consulting with Leer.  

 
Auto-Defrost Control:

  

The AD control is located under the condensing 
unit cover and contains two thermal-couple probe 
wires. Both probe wires are routed through the 
cabinet’s suction line hole and into the unit cooler 

assembly, which is mounted to the interior ceiling 
of the cabinet. The Red Air Sensing Probe (“P1”) 
routes through the unit cooler and has its’ sensing 
bulb secured to the outer, left-hand wall of the 
unit cooler. Probe “P1” monitors the air 
temperature in the merchandiser at that location. 
During the normal operation of the control, the 
digital display will show the cabinet temperature 
at the probe “P1” location. The Black Probe “P2” 
is inserted into the finned section of the 
evaporator coil, near the top of the unit cooler 
assembly. This probe monitors the temperature of 
the evaporator coil during the defrost cycle.  

 
Electronic Control Startup:  

Turn the switch if equipped into the ON position

After a 2-minute delay, the compressor and the 
condenser fan should start.

 The light fixture 

should start immediately when power is applied. 
After a 2-minute delay, the compressor and the 
condenser fans should start. The evaporator fans 
will start once if the evaporator temperature is 
under 75°F. The condensing unit will continue to 
run until the air temperature in the cabinet reaches 
+14-16°F.  
 

Note:

 If a defrost is required upon startup the 

controller will enter defrost mode after the 2-
minute delay. Normal operation will resume upon 
defrost termination and a short drip time.  

Possible Displayed Alarm Codes:   

 
“P1” – Air Probe failure: The control will 
override the “P1” functions and cycle the 
compressor at preset time intervals, until the 
probe fault can be corrected. 
 
“P2” – Evaporator Probe failure: The control will 
override the “P2” function and operate with a 
timed defrost cycle, until the probe fault can be 
corrected. 
 
“HA” – Maximum Temperature Alarm: The 
cabinet air temperature has exceeded programmed 
temperature for a period exceeding a preset time. 
The alarm will continue to display until the 
cabinet temperature drops below maximum levels. 
 

Summary of Contents for R290 PL

Page 1: ...800 766 5337 www leerinc com R290 PL and TD MERCHANDISER INSTALLATION OPERATION AND SERVICE MANUAL WARNING This product can expose you to chemicals including nickel which is known to the State of Cal...

Page 2: ...r manual owner s guide before attempting to service this product All safety precautions must be followed CAUTION Risk of fire or explosion Dispose of properly in accordance with federal or local regul...

Page 3: ...d Alarm Codes 6 Loading Ice 7 Maintenance and Service 7 Cleaning the Merchandiser 7 Cleaning Door Gaskets 7 Cleaning Condenser Coils 8 Defrosting the Merchandiser 8 Auto Defrost Electronic Control 8 G...

Page 4: ...iser installation location should have a solid level base If the merchandiser is exhibiting a slight forward lean the front of the cabinet should be blocked to bring the cabinet to a level position A...

Page 5: ...vaporator Indoor auto defrost models are supplied with a condensate evaporator heater assembly which is packaged and shipped inside the merchandiser It will require simple installation by the consumer...

Page 6: ...and contains two thermal couple probe wires Both probe wires are routed through the cabinet s suction line hole and into the unit cooler assembly which is mounted to the interior ceiling of the cabine...

Page 7: ...a flammable and explosive gas Component parts shall only be replaced with like components Maintenance and repair of the electrical and refrigeration systems should only be done by licensed trained and...

Page 8: ...consumer needs to install the condensate evaporator heater assembly described in the Installation section of this manual onto the exterior back wall of the cabinet The melt water from the defrost cyc...

Page 9: ...uce stretching If the door gasket appears to be in good condition but is failing to seal to the surface of the cabinet both the spring load tension and adjustment of the hinges should be checked Solid...

Page 10: ...nit charged with R290 is not serviceable on a consumer level Experienced technicians can contact Leer for an in depth service and guideline manual The use of special tools and proper procedures perfor...

Page 11: ...pring and place the Adjustment Collar over the round pin Fig 2 4 Using the Adjustment Pin turn the Adjustment Collar until the Pin contacts the Hinge Then insert the Stop Pin in hole of Adjustment Col...

Page 12: ...s to interfere with the new gasket installation 4 Align new gasket with door corners and use thumb to press into frame 5 Start at one corner of the frame and begin pressing the new gasket into the slo...

Page 13: ...d in compliance to UL Standard 471 Replacement parts that are not UL Certified or are not identical to the OEM installed part will void the merchandiser s UL Listing and or the Factory warranty Contac...

Page 14: ...cated below the threshold of the pallet load Connect each ramp by the grove and stud Repeat this process for ramp 3 Repeat for ramp 4 Move the ice into the Pallet Load Set the ice into place and remov...

Page 15: ...a pallet jack by the base pallet Move the box into place firmly against the aluminum back stop Lower the pallet jack and remove the base pallet The unit has a rubber gasket that will seal the unit fro...

Page 16: ...for repair or replacement of any defective part s or assembly only for defects reported to Seller within ninety 90 days after the date of installation ALL LABOR CHARGES SHALL BE AUTHORIZED OR APPROVE...

Reviews: