The Installation must be carried out by an electrician

LED Group 

 

 

Western Retail Park 

         Tel: +353 1 7099000 

Nangor Road 

 

         Fax: +353 1 7099060

Dublin 12  

 

         Email: [email protected] 

Ireland   

 

         Website: www.led.ie

Page 1

ISO 9001:2008

Q UAL IT Y ASSU RED CO MPANY

Issue 1 220110 

Information for the Product user

1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste (WEEE 

    marked with crossed out wheelie bin symbol). 

2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre 

    for waste electrical equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.

3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly.  It is 

    important that it is separated from normal household waste and recycled in the WEEE chain

4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household 

    waste, but should be disposed of according to local WEEE regulations

Specification:

Installation:

Model No. 

 

 

            R8EM 

                   

Operating mode   

 

            maintained           

Lamp   

 

 

            T5 8W fluorescent tube

Dimensions 

 

 

            (L)430mm x (H)200mm x  60mm

Insulation 

 

 

            Class I, Must be earthed

Supply voltage   

 

            240V 50Hz

Lumen oupput                                               15

Supply current   

  

            0.1A 

 

             

Discharge Duration 

 

            >3 hours after minimum 36Hr charge

Battery   

 

 

            2.4V x 4Ah Ni-Cd cells

Battery Life 

 

 

            up to 4 years normal use

Storage temperature 

 

            -5°C ~ +60°C

Operating ambient temperature 

            5°C ~ +25°C

Case materials   

 

            Steel/ PC sign panel

Flammability 

 

 

            With stands 850°C Glow wire test

Connection:   

 

 

            Screw terminals

Suitable for mounting on a normally flammable surface

Green LED indicator indicates battery charging mode

Safety and performance in accordance with EN60598-1, EN60598-2-22

EN50082-1, EN61000-3-2, EN61000-3-3

Suitable for Indoor use, wall mounted

! Warning. Isolate mains supply before installing or servicing

1. Remove front panel and gear tray and knock out relevant cable entry point

2. Mark appropriate fixing points on wall; check that fixings  will not impinge on 

    concealed cables of pipes before drilling holes.

3. Introduce supply cable. ( Normally, the emergency fitting must be

    powered from the lighting circuit  feed)

4. Write installation date on battery

5. Connect wires from unswitched supply from a tamper proof test switch (key operated 

    with automatic re-set), brown to “PL”, Blue to “N”  and green/yellow to earth marked 

    terminals on gear tray. In the maintained emergency unit;

        for lamp always on, link “PL” to terminal  “SL”

        for  lamp switched connect switched live wire to terminal “SL”

    

Note:

 if “SL”  not connected, fitting works as non-maintained

6. Fix gear tray in position and refit appropriate panel.

7. Switch on supply: In the non-maintained unit the green led should come on indicating 

    correct battery charge has started. The lamp only lights  if the mains supply fails. 

    In the maintained unit, the green led will come on indicating correct battery charge has 

    started and the lamp will light (if switched live on).  When supply to the unswitched live 

    is lost, battery will operate lamp in emergency mode.

R8EM 

Maintained Exit sign bulkheads

 

Please read instructions before commencing installation and 

retain for future reference.

incl.