User Manual for ELP Servo
www.leadshine.com
149
3. Trigger fixed path by Pr8.02
4. Or write in immediate data into Pr9.00-9.07, set Pr9.07=0x10, implement immediately running path 0.
For example
:
Order
Sending orders
(
Master->Slave
)
Return command (Slave->Master
)
1
ID
Sub-station No.
0~31
ID
Sub-station No.
0~31
2
FC
Function code
0x10
FC
Function code
0x10
3
ADDR
Address
0x62
ADDR
Address
0x62
4
0x00
0x00
5
NUM1
Data quantity Word
0x00
NUM
Actually written data
quantity
0x00
6
0x08
0x08
7
NUM2
Data quantity Byte
0x10
CRC
check code
L
H
8-9
Pr9.00
Mode
XXXX
10-11
Pr9.01
High position
XXXX
12-13
Pr9.02
Low position
XXXX
14-15
Pr9.03
Speed
XXXX
16-17
Pr9.04
Acceleration
XXXX
18-19
Pr9.05
Deceleration
XXXX
20-21
Pr9.06
Delay time
XXXX
22-23
Pr9.07
Trigger control
0x0010
24
CRC
Check code
L
25
H
Please refer to parameter specification for specific data setting.
9.5 Operation case
9.5.1 IO trigger case
Pr-Mode motion can be triggered by IO signal.
1
、
Parameters setting as follows:
Parameters
Name
Specification
Pr0.01
Control Mode Setup
Set Pr0.01=6 for Pr-Mode
Pr4.00
SI1 Input selection
Set 83 for internal SERVO-ON
Set 03 for external SERVO-ON
Pr4.00-Pr4.08
SI input selection
Specific of the 9 input terminals' function distribution
,
refer to functional allocation table.
Pr4.10-Pr4.15
SO output selection
Specific of the 6 output terminals' function
distribution
,
refer to functional allocation table.