User Manual Of ELP AC Servo
117
www.leadshine.com
Relevant parameters setup of torque control mode
8.3.1 Analog torque command input
The analog torque command input voltage is converted to equivalent digital torque command. You can set
the filter to eliminate noise or adjust the offset.
Pr3.17
Name
Selection of torque command
Mode
T
Range
0
、
1
、
2
Unit
Default
0
Data Type
16bit
Access
R/W
Address
0323H
Repower
-
Setup value
Torque command input
Velocity limit input
0
Analog input 3
Parameter value (P3.21)
1
Analog input 3
Analog input 1 for Speed limit
2
Parameter value (P3.22)
Parameter value (P3.21)
3
Analog input 3
Speed limit 0
Pr3.18
Name
Torque command direction
selection
Mode
T
Range
0~1
Unit
—
Default
0
Data Type
16bit
Access R/W
Address
0325H
Repower
-
Select the direction positive/negative direction of torque command
Setup
value
Details
0
Specify the direction with the sign of torque command
Torque command input[+] positive direction, [-] negative direction
1
Specify the direction with torque command sign(TC-SIGN).
OFF: positive direction ON: negative direction
Pr3.19
Name
Torque command input gain
Mode
T
Range
10~100
Unit
0.1V/100%
Default
0
Data Type
16bit
Access R/W
Address
0327H
Repower
-